FLSTDMFC0A pCO² refrigeration system
cod. Carel +030221991 rel. 1.0 dated 27/07/01
36
3$5$0(7(57$%/(6
'HIDXOWYDOXH
The following table provides a complete list of the values set as default (parameters set by automatic installation),
In addition, a column is available for the users to write their own settings.
9DULDEOH
'HVFULSWLRQ
GHIDXOW
OLPLWV
XQLW
SET_COMP
compressor set point
1.0
can be set
bar
DIFF_COMP compressor
differential
5 0
/
2.0
bar
MIN_SET_COMP
minimum compressor set point limit
2.5
-9.9/99.9
bar
MAX_SET_COMP
maximum compressor set point limit
0.1
-9.9/99.9
bar
SET_FAN
fan set point
15.5
can be set
bar
DIFF_FAN
fan differential
2.0
0/ 20.0
bar
MIN_SET_FAN
minimum fan set point limit
1.0
-9.9/99.9
bar
MAX_SET_FAN
maximum fan set point limit
25.0
-9.9/99.9
bar
SET_VENT_INV
fan inverter set point
15.5
10 / 25
bar
DIFF_VENT_INV
fan inverter differential
1.5
0.2 / 2
bar
SG_ORE_COMP
Compressor operating hour threshold
1000
0 / 99999
hours
THRESH_HIGH1
High inlet threshold
5
0.1 / 6
bar
DIFF_HIGH1
High inlet differential
0.5
0.1 / 2
bar
THRESH_HIGH2
High outlet threshold
18.5
15 / 30
bar
DIFF_HIGH2
High outlet differential
1
0.2 / 4
bar
THRESH_LOW1
Low inlet threshold
1
-0.5 / 5
bar
DIFF_LOW1
Low inlet differential
0.5
0.1 / 1
bar
THRESH_LOW2
Low outlet threshold
10.0
5 / 30
bar
DIFF_LOW2
Oil differential alarm delay
120
0 / 360
s
RIT_ALLARMI
Alarm relay delay
0
0 / 999
s
RIT_DIF_OLIO
Liquid level alarm delay at start
90
0 / 360
s
RUN_DELAY_OILD
Liquid level alarm delay when running
10
0 / 360
s
TIME_SWITH_ON1
Compressor start request delay
20
10 / 360
s
TIME_SWITH_OFF1
Compressor stop request delay
10
10 / 360
s
TIME_MIN_ON
Minimum compressor ON time
60
10 / 360
s
TIME_MIN_OFF
Minimum compressor OFF time
120
10 / 360
s
TIME_BETW_COMP
Time between two starts of different compressors
20
0/9999
s
TIME_SAME_COMP
Time between two starts of the same comp
360
240 / 600
s
UNLOAD_DELAY
Capacity-control step delay time
20
0 / 999
s
TIME_SWITH_ON2
Time between fan starts (ZN)
2
0 / 999
s
TIME_SWITH_OFF2
Time between fan stops (ZN)
2
0 / 999
s
TIME_BETW_FAN
Time between two starts of different fans
5
0 / 999
s
N_COMP
Number of compressors
4 SMALL board
4 MEDIUM board
5 LARGE board
1 / 6
TYPE_INPUT_X_COMP
Type of inputs per compressor
1 SMALL board
2 MEDIUM board
3 LARGE board
1 / 3
ABIL_ROTAZ_COMP
FIFO rotation compressors
Yes
Yes / No
EN_ROT_FAN
FIFO rotation fans
Yes
Yes / No
N_VENT
Number of fans
4 fan.
EN_INV_COMP
Compressor inverter
No
Yes / No
EN_INV_FAN
Fan inverter
Yes
Yes / No
EN_KEYB_ON_OFF
Enable off from keypad
No
Yes / No
STOP_SONDE
Off from probe fault
No
Yes / No
EN_OFF_SUPERVISOR
Enable on/off from supervisor
No
Yes / No
input_logic INPUT_LOGIC
Input logic
N.C.
N.O. N.C.
UNLOAD_LOGIC
Capacity-control step logic
N.C.
N.C. / N.O.
TYPE UNIT
Type of system
TN
LT / NT
TYPE_FREON
Type of freon
R22
---, R22, R134a,
R404a, NH3, R12
BAUD_RATE
Communication baud rate
19200
19200
bps
IDENT
Identification number for supervisor
1 0
/
200
NEW_PASS_UTENTE User
password
0000
0
/
9999
NEW_PASS_MANU
Service
password 0000
0
/
9999
NEW_PASS_COST
Manufacturer password
1234
0 / 9999
FSC_MIN_MAND
Minimum
outlet
-1
bar
FSC_MAX_MAND
Maximum
outlet
19
bar
FSC_MIN_ASP
Minimum
inlet
-1
bar
FSC_MAX_ASP
Maximum inlet
19
-2
bar
7DEOH