32
GB
easy way ARIA +030220841 - rel. 1.0 - 26.10.2007
To access the information on the easy way system, the master-supervisor
must have the following settings:
CAREL master protocol;
•
baud rate 19200.
•
Below are the tables of supervisor variables for the components in the
system.
5.1 Access point variable list
par.
description
min
max
def
UOM type
index
R/W notes
-
Domain opening status
0
1
-
-
D
2
R
0= Network closed
1= Network open
-
Enable open/close domain
(see command set for variable I12)
0
1
-
- D
3
R/W
0= standard operation
1= enable command I13
-
Device CAREL address
1
15
-
-
I
2
R
-
Number of sensors presenti
0
60
-
-
I
9
R
-
Commands (enabled with D3)
5266
Open network domain for associating the devices
5267
Close network domain for associating the devices
0
65535
-
- I
13
R/W
Tab. 5.a
5.2 Terminal variable list
par.
description
min
max
def
UOM type
index
R/W notes
-
Ambient temperature
T&H
T
T&H
T
--
°C
A
1
R
-20.0 -7.0 80.0 55.0
-
Ambient humidity (99.9 temperature-only model)
1.0
---
100
---
--
%rH
A
2
R
-
Battery level
0.0
100.0
--
%
A
3
R
-
Minimum temperature variation to force transmission
0.1
5.0
1.0
°C
A
4
R/W
-
Minimum humidity variation to force transmission
1.0
10.0
5.0
%rH
A
5
R/W
-
Temperature set point
8.0
32.0
25.0
°C
A
6
R/W
-
Humidity set point
0.0
100.0
50.0
%rH
A
7
R/W
-
Indicative wireless signal level
-100.0
-30.0
--
Dbm
A
8
R
-
Temperature delta in COMFORT
-5.0
5.0
0.0
°C
A
9
R/W
-
Temperature from supervisor if D11=1
-40.0
80.0
0.0
°C
A
10
W
-
Humidity from supervisor if D11=1
1.0
100.0
0.0
%rH
A
11
W
-
Dead band for temperature calculation algorithm (AUTO mode)
0.0
25.0
0.0
°C
A
12
W
-
Humidifi cation algorithm diff erential
0.0
algorithm disabled
0.0
25.0
5.0
%rH
A
13
W
-
Heating/cooling algorithm diff erential
1.0
10.0
1.0
°C
A
14
W
loc 5
Ambient temperature sensor calibration
-9.5
9.5
0.0
°C
A
15
R/W
loc 6
Ambient humidity sensor calibration
-10.0
10.0
0.0
%rH
A
16
R/W
loc 4
Temperature delta in Sleep mode (night)
-5.0
5.0
0.0
°C
A
17
R/W
-
Local temperature sensor alarm
0
no temperature sensor alarm
1
temperature sensor alarm
0
1
-
D
4
R
-
Local humidity sensor alarm
0
no humidity sensor alarm
1
humidity sensor alarm
0
1
-
D
5
R
-
ON/OFF
0
terminal off
1
terminal on
0
1
1
D 6
R/W
-
Sleep mode status
0
instrument not in sleep mode
1
instrument in sleep mode
0
1
0
D 7
R/W
-
Occupancy mode status
0
deactivated
1
active
0
1
0
D 8
R/W
-
Humidifi cation request
0
request not active
1
request active
0
1
-
D
9
R
5. SUPERVISOR