19
GB
easy way ARIA +030220841 - rel. 1.0 - 26.10.2007
Clock from terminal
Fig. 4.c.f
Key:
enter clock setting mode when pressed and held for 5 seconds.
The clock can now be set, with the hour digits fl ashing
Enter the current hours using the UP and DOWN buttons
•
Press
•
to select MINUTES
Enter the current minutes using the UP and DOWN buttons
•
To exit clock setting mode::
By time around 30 sec after the last button was pressed
•
manually by pressing
•
Clock from the supervisor
Setting the clock from the supervisor::
Enter the synchronised hours and minutes for variables I10 and I11.
•
Enable synchronisation by setting D13 =1.
•
par.
description
min
max
def
UOM
type
index
R/W
notes
-
Synchronise time function
0
Local time
1
Enable write time from supervisor (I10, I11).
When written the value returns to 0
0
1
0
-
D
13
R/W
-
-
Terminal hours
0
23
-
Hours
I
8
R
-
-
Terminal minutes
0
59
-
Min
I
9
R
-
-
Supervisor hours. Write enabled using D13
0
23
-
Hours
I
10
W
-
-
Supervisor minutes. Write enabled using D13
0
59
0
Min
I
11
W
-
Tab. 4.e
Time display
Parameter loc 3 is used to choose the type of time display: 12/24 h.
par.
description
min
max
def
UOM
type
index
R/W
notes
loc 3
Time display mode
0
24 h
1
12 h
0
1
0
-
D 16
R/W
-
FRESH AIR button (3)
Set the % of outside air mixed (mainly for applications with ARIA).
Pressing the button once displays the %FA already set in the main
•
fi eld.
Each time the UP/DOWN button is pressed increases/decreases the
•
%FA in steps of 1%FA.
To exit the FRESH AIR function:
By time, 5 seconds after the last button is pressed
•
manually by pressing the button.
•
Display and/or set from the supervisor
par.
description
min
max
def
UOM
type
index
R/W
notes
-
Fresh Air percentage
0
100
50
%
I
7
R/W
-