41
ENG
Control
WTS +0300130EN rel. 1.0 - 05.09.2022
11.6.9 Calibration high pressure monitor
(only ROL / ROC140) PS
HIGH
The system operating pressure can be controlled by
means of a pressure switch between the high pressure
pump and the RO modules. If a maximum pressure set
on the pressure switch is reached during production
(e.g. due to an overly restricted concentrate valve), the
system can be stopped.
8 MAX PRESSURE
9 PUMP TEMP IN
8A HIGH PRESSURE
ENABLED
»
Press the arrow keys
éê
to select if pressure
switch should be active or inactive.
»
Confirm the selection with
.
The program jumps to submenu "8B".
8B HIGH PRESSURE
CONTACT N.C.
»
Press the arrow keys
éê
to set the switching
direction.
N.O. CONTACT = The input functions as a normally open
contact.
N.C. CONTACT = The input works as a normally closed
contact
»
Confirm the selection with
.
The program jumps to submenu "8C".
Notice: N.C. contact is set ex works. Do not change
this! Otherwise there is a risk of damage to the
system.
8C INPUT DELAY
00Sec
»
Press the arrow keys
éê
to set the time of
delay
0 Sec = no delay
(see note at the end of the chapter)
»
Confirm the selection with
.
The program jumps back to the main menu.
»
Default value: 00 sec
Menu item 9: "High pressure pump TSHP " is not
active.
9 PUMP TEMP IN
10 SOFTENER
11.6.10
Upstream softening
system
INFIL
If the upstream softening system is e.g. equipped with
an automatic backwashing device and has a potential-
free switching con-tact to show the backwashing, then
the control system can shut down the WL-ROC system
for the duration of the filter backwashing and put it on
hold.
It is also possible to connect an upstream 1-col-umn
softening system to the control so that the RO unit goes
into standby mode for the duration of the regeneration.
10 SOFTENER
11 SPUELUNG
10A SOFTENER
ENABLED
»
Press the arrow keys
éê
to select if relay
input should be active or inactive.
»
Confirm the selection with
.
The program jumps to submenu "10B".
»
Default value: Disabled
10B SOFTENER
CONTACT N.O.
»
Press the arrow keys
éê
to set the switching
direction.
N.O. CONTACT = The input functions as a normally open
contact.
N.C. CONTACT = The input works as a normally closed
contact
»
Confirm the selection with
.
The program jumps to submenu "10C".
»
Default value: NC
10C INPUT DELAY
00Sec
»
Press the arrow keys
éê
to set the time of
delay.
0 Sec = no delay
(see note at the end of the chapter)
»
Confirm the selection with
.
The program jumps back to the main menu
»
Default value: 00 sec