MRF 16/22
26
MF 55-GB 1.21
8.4
To pause (hold) a program
Press RUN/HOLD once.
8.5
To stop and reset a program
Press RUN/HOLD once, then press again and hold for 2 seconds.
8.6
To run a different program
To select a program:
From the home page, press page
once to get to the Program Status page.
Press up
S
to select a program number.
Start the program by pressing RUN/HOLD twice.
8.7 Program
cycling
The Cycles parameter sets the number of times the program will run.
The default setting is 1 cycle.
To change the number of cycles, press page
twice, then press scroll
3
until the display
shows “Cycles”, then press up
S
to set a finite number of cycles up to 999. Or press down
T
to set cycling to continuous.
8.8 Program
status
While a program is running the home display shows several values
[See figure 5.2]
:
OP1: Element power on
1:
MW power on. Percentage level as set on the Microwave control page.
1 2: MW power on. Percentage level as set for the program segment.
Measured temperature
Program setpoint temperature (PSP)
MW power percentage
To see more detail:
Press page
once to go to the program status page. The measured temperature remains on
the top of the screen. The lower half of the screen now shows:
Current program number
Press
3
to view the current segment number and type
Press
3
to view the time remaining for that segment
Press
3
to view the status. This can be changed to Hold, Reset or Run by pressing up
S
or
down
T
.
Press
3
to view the program setpoint (PSP)
Press
3
to view the current Segment Type. Step and Call segments are instant, so are only
flashed on the screen, unless Holdback is operating on that segment.
Press
3
to view the target Setpoint
Press
3
to view the segment Rate For Rate, Time and Step segments only
Press
3
to view the cycles left
Press
3
to view the events
Press
3
to view the program Time Left