36
Space HMI Operation
Accessing Menu Configurations
The HMI allows the user to change parameters and options. The user may use the HMI to view operating information
regarding sensors, temperatures, pressures, and fault history on the HMI screen. There are four buttons to navigate
through the HMI screens.
NOTE: Buttons change functions during certain options and tests. Verify the screen and buttons throughout the
menu display.
The user can access the Top Menu HMI configurations by pressing the top two buttons simultaneously. To exit this
scre
en, simply press the ‘BACK’ button. When setting certain options or functions, pressing the ‘BACK’ button multiple
times will bring up the save screen. The user may select ‘YES’ to save the changes, select ‘NO’ to return to factory
settings or select ‘CANCEL.’ When selecting ‘CANCEL,’ any changes made will not be saved, and the screen will return to
the top menu.
The HMI menu system allows full access to every configurable parameter in the HMI. The parameters are factory
configured to the specific application. Parameters may need to be modified to fine-tune automatic operation after the
original setup.
Remote (HMI) Control Panel
On units shipped with a space HMI, a Cat 5 cable will need to be run from RTULink board J4 to J2 on the HMI. If
additional space HMIs have been added, they can be daisy-chained from the first HMI. An end of line resistor should be
added to the last HMI in the chain.
Space HMI Menu Structure
User settings
: Allows the user to change or set certain temperature and configurations on the unit. Any changes within
this menu do not require a reboot to take effect.
Factory settings
: Requires a password to enter this menu (1 1 1 1). These will be set job specific from the plant. Any
changes within this menu require a reboot to take effect. Upon exiting factory settings, if anything has been altered, the
board will reboot itself.
Service
: Requires a password to enter this menu (1 2 3 4). Allows a certified technician to monitor the unit, and test
components in the system.
Space HMI Functionality
User Settings
Temp Set Points
– Some or all of these may not be available based on settings. The user will be allowed to
check or adjust the set points for Heating, Cooling, and Options that are enabled on the system.
Blower Settings
- Blower mode is the blower's default status that the RTULink defaults to if it ever comes out of a
schedule from CASLink or has never received a schedule from CASLink (during startup).
Scheduling
– Top menu to set schedule options.
Scheduling Times
– To set a schedule for a specific day and time. There are four slot schedules (A, B,
C, D). Select the slot schedule, and select a start and end time for the schedule.
Copy Schedule
– Once a schedule is set for a day and time, that set schedule can be copied from one
day to the next.
Override Sch
– To override a schedule, select the appropriate schedule slot that will need to be
overridden.
Unocc Def Set Points
– When the system is in an unoccupied state, use this menu to set unoccupied set
points.
Active Faults
– Contains the current faults on the board.
Fault History
– Displays time-stamped history of the last 20 faults, most recent fault showing first.
Summary of Contents for RTULink
Page 2: ...2...
Page 30: ...30 Main Board HMI Menu Tree...
Page 31: ...31...
Page 32: ...32...
Page 33: ...33...
Page 34: ...34...
Page 41: ...41...
Page 42: ...42...
Page 43: ...43...
Page 44: ...44...
Page 52: ...52 APPENDIX C Fixed Dry Bulb Economizer Figure 34 Fixed Dry Bulb Economizer Operation...
Page 53: ...53 Differential Dry Bulb Economizer Figure 35 Differential Dry Bulb Economizer Operation...
Page 54: ...54 Fixed Enthalpy Economizer Figure 36 Fixed Enthalpy Economizer Operation...
Page 55: ...55 Differential Enthalpy Economizer Figure 37 Differential Enthalpy Economizer Operation...