Lock Output Relay Wiring – Standalone Reader
DC ELECTRIC STRIKES – DIFFERRENT POWER SOURCE
NOTES
:
1.
Use 1N400x series diode as shown, to prevent “back EMF” from
damaging the reader.
2.
Ensure that the lock power is 12VDC (Maximum 30VDC) with sufficient
current to power the lock (Maximum 1A).
See lock specifications from
manufacturer
. The reader requires 12VDC/500 mA.
(Supplied transformer)
Power source
for the lock
only
2
Power source for
the reader only
Important
: Dry contact relay rating: Max. 30VDC, 1A