WIRING (SMARTLOCK)
1
2
3
4
5
6
7
8
O
N
COMMS
LED
R
S
-4
8
5
SHIELD
B A GND
GND
+12 VDC
O
N
8
1
+
5
V
+
1
2
V
N/O
N/C
O
F
F
N/C
N/C
N/O
N/O
- Each Smartlock controller must
have a unique address
- For communication wiring, use 22
AWG, twisted pair, stranded,
shielded cable, 2000ft (
) MAX
total length.
609 m
- Canlan needs to be configured for
RS-485 communications. Refer to
the Canlan Installation and
Configuration guide for details.
NOTES:
ADDRESS “1” SHOWN
(Dipswitch 1 is OFF)
CANLAN
TCP\IP CONTROLLER
SMARTLOCK
CONTROLLER
#1
O
N
O
F
F
O
N
8
1
+
5
V
+
1
2
V
ADDRESS
SWITCH
B A GND
B A GND
SHIELD
GND
+12 VDC
SMARTLOCK
CONTROLLER
#2
TO OTHER
SMARTLOCK
CONTROLLERS
- 30 CONTROLLERS MAXIMUM
- 609 m (2000 ft.) MAXIMUM LENGTH
Option 1:
12 VDC
AC-DC Adaptor
OR
- It is highly recommended that the
Canlan be powered by 12 VDC
output from a Cansec access control
panel with battery backup. This will
prevent connectivity loss during a
power outage.
POWER:
Option 2:
GND
+12 VDC
–
+
NOTE:
The EIA RS-485
standard does not permit
T-Tap or Star connections.