Default First Screen
Two group of Protection Setting are available in CSDPR-V2 relay. User can select
One Group as Active Group. For setting below are simple steps for configuration:
Default Password for settings : “ 4-Times Enter Key”
MAIN DEFAULT SCREEN PAGE:
The very first Screen of the HMI shows the Measured Primary Current for all the
phases based on CT ratio.
L1
: 0000.0 A
L2
: 0000.0 A
<Menu 1>
(EDIT/VIEW PARAMETERS)
By using
the
scroll keys
select the
desired
menu and
press
ENTER.
Press Key
FACTORY MODE Setting are not for the users.
How to do Settings
*
Note : -
*
Menu Model Dependent
#
/
#
EDIT VIEW
<
> : For Active Group Selection of Parameter
GROUP SELECT
<
> : Protection Related Parameter Menu
PROTECTION
<
> : Cold Load Protection Menu
COLDLOAD PRT
<
> : Fault Record Menu
FAULT RECORD
<
> : Event Record Menu
EVENT RECORD
<
> : Programmable Relay Assignment Menu
DO ASSGNMNT
<
> : Programmable Relay Reset Menu
DO RESET
<
> : Trip Type
TRIP TYPE
<
RST TRIP CNT
> : Reset Trip count Menu
<
> : Display Options Menu
DISPLAY OPTN
<BATTRY STATS
> :
Menu
Battery Status
<
> : Output Trip Test Menu
TRIP TEST
<
> : Communication
485 Menu
COMMN SETTNG
RS
<
> : Load Default Menu
LOAD DEFAULT
<
> : Clock Setting Menu
EDIT RTC
<
> : Password Change Menu
CHNGE PSWORD
<
> : Factory Setting Menu
FACTORY MODE
<
> : Relay Version Menu
RELAY VERSON
←
BACK