The  recommendations  contained  in  this  section  are  designed  to  assist  you  in  reducing  false  alarms.   The  first  column  contains
the  Command  Locations and  Digit  Positions  in  parentheses  (  ).  The  second  column  is  the  recommended  program  option  followed
by  a  brief  explanation.

Program Option

Program Option

Program Option

Program Option

Program Option

CL

CL

CL

CL

CL

Program Function

Program Function

Program Function

Program Function

Program Function

Comments

Comments

Comments

Comments

Comments

Arming/Combination

09 (2)

Combination

This feature is enabled to prevent unauthorized users from

Options

Command

activating certain keypad functions.  When activated, this
command will require a valid User Combination to perform such
functions as Bypassing a Zone, Group Bypassing, Keypad
Activated RPS, Central Station and Bell Testing, and Instant
Arming.  For additional assistance with commands requiring
User Combinations, see page 21 (Command Summary).

Arming/Combination

09 (4)

Chirp Alert

This option minimizes the possibility of leaving the system

Options

unarmed (faulted) when exiting.  The system is armed in the

normal manner and the user exits through the delayed exit door.
If the door does not close properly, returning the loop to the
normal state, the system will transition from the Exit Delay to the
Entrance Delay at the completion of the Exit Delay time and chirp
the Bell, alerting the user to the error in arming the system.

Loop  Control

1F  -  26  &

Loop  Response

This option determines the response time of the loop itself.  It acts

49 - 50 (2)

Time

as a buffer on the loop to minimize the possibility of fast acting
sensors, such as swingers or window foil, producing false
alarms.

Loop  Control

1F - 26 &

Loop Restore Type

This option is used in conjunction with CL 17 - 1E & 40 - 47 Digit

49 - 50 (3)

Positions (3 & 4), Restore Reporting Code, and CL 2A (2),
Restore Receiver Select.  The panel can be programmed to send
a Restoral Report only when the loop is normal and the system
is disarmed.  With this arrangement, any loop which is triggered
multiple times while armed will only send one alarm report until
the system is disarmed.  This prevents the system from tieing up
the phone line with continuous alarm and restoral reports.

Loop  Control

1F  -  26  &

Loop  Arming  Type

There may be occassion where it is desirable to program all doors

49 - 50 (4)

and interior points as delayed.  Or you may need to program
interior zones to be delayed only during the Entry/Exit Delay
Time.  This Command Location allows a variety of Arming Types
to help minimize false alarms.

Event Reporting

2A (5 & 6)

Cancel Report Code/ This feature should always be enabled on reporting systems,

Cancel Report

especially if the system does not send Opening and Closing

Receiver  Select

Reports.  A Cancel Report is sent to the monitoring station in the
event that an Authorized User clears the alarm while the bell is
still active.  The Cancel Report Code (Digit Position 5) is actually
a  two-digit  code with the first digit being programmed by the
installer and the second digit being the User ID # when the report
is sent.  Digit Position (6) determines which receiver gets the
Cancel Report.

Recommendations for Reducing False Alarms

Summary of Contents for SYS3316RF

Page 1: ...ED BY FUSE F2 3AG 0 75A P N 5 051 396 00 Rev A P N 5 051 396 00 Rev A P N 5 051 396 00 Rev A P N 5 051 396 00 Rev A P N 5 051 396 00 Rev A All outputs are power limited Connect ground wire from door h...

Page 2: ...3 House hold Burglar Alarm System Units and UL 1635 Digital Burglar Alarm Communicator System Units The following programming restrictions must be observed to meet UL standards UL COMPLIANCE UL COMPLI...

Page 3: ...rmer to the wall DO NOT share the secondary of the transformer with other devices A foreign ground can damage the power supply voiding the warranty DO NOT use any transformer other than that specified...

Page 4: ...p seized 9 X PCF The 9 X PCF has eight flying leads on the other end Wire them to the phone line terminals as follows If you replace the battery after a SYSTEM TROUBLE LOW BATTERY message you must tes...

Page 5: ...terior SUPERVISED EOL circuit Zone 15 interior SUPERVISED EOL circuit Zone 16 interior SUPERVISED EOL circuit Emergency soft zone chirp audible non reporting Fire soft zone pulsed audible non reportin...

Page 6: ...ations A0 B3 and B4 with an LED keypad remember to enter the Command Location followed by the program data then press the key Warning If you enter a Command Location and then press the key without ent...

Page 7: ...to the Alpha keypads The template shown on the next page should be used when program ming the keypad To activate the keypad programming mode enter the Installer s Code 0 1 Information may be entered i...

Page 8: ...4 61 User 25 62 User 26 63 User 27 64 User 28 65 User 29 66 User 30 67 User 31 68 User 32 0 Arm Only with Closing Report Shunting Allowed 1 Disarm Only with Opening Report Shunting Allowed 2 Arm and D...

Page 9: ...ions Formats Command Location 0A Communications Formats Command Location 0A Communications Formats Command Location 0A Communications Formats 1 2 3 4 1 2 1 2 DefaultValues DefaultValues DefaultValues...

Page 10: ...n Digit Position 6 Dialing Attempts 1 1 try 2 2 tries 3 3 tries 4 4 tries 5 5 tries 6 6 tries 7 7 tries 8 8 tries 9 9 tries 0 10 tries 1 11 tries 2 12 tries 3 13 tries 4 14 tries 5 15 tries 1 2 3 4 5...

Page 11: ...mmand Location 0F Receiver 1 Phone Number digits 13 18 Command Location 0F Receiver 1 Phone Number digits 13 18 Command Location 0F Receiver 1 Phone Number digits 13 18 Command Location 0F Receiver 1...

Page 12: ...Receiver 2 Phone Number digits 7 12 Command Location 12 Receiver 2 Phone Number digits 7 12 Command Location 13 Receiver 2 Phone Number digits 13 18 Command Location 13 Receiver 2 Phone Number digits...

Page 13: ...igit Position 1 Alarm Receiver Select Digit Position 1 Alarm Receiver Select 0 Receiver 1 with Receiver 2 as back up 1 Receiver 1 only 2 Receiver 2 only 3 Receiver 1 and Receiver 2 Dual Reporting 0 5...

Page 14: ...3 Fire Receiver Select Digit Position 3 Fire Receiver Select Digit Position 3 Fire Receiver Select Digit Position 3 Fire Receiver Select Digit Position 4 Loop Bell Type Digit Position 4 Loop Bell Typ...

Page 15: ...porting Digit Position 5 Cancel Report Code Digit Position 5 Cancel Report Code Digit Position 5 Cancel Report Code Digit Position 5 Cancel Report Code Digit Position 5 Cancel Report Code Valid entrie...

Page 16: ...ress Report and Delays Digit Position 4 Exit Delay Time Digit Position 4 Exit Delay Time Digit Position 4 Exit Delay Time Digit Position 4 Exit Delay Time Digit Position 4 Exit Delay Time DefaultValue...

Page 17: ...mand Location 2F Unit Control Command Location 2F Unit Control Command Location 2F Unit Control DefaultValues DefaultValues DefaultValues DefaultValues DefaultValues 1 2 3 4 5 0 0 1 1 1 2 2 2 2 2 F F...

Page 18: ...rts Command Location 48 Trouble Reports Command Location 48 Trouble Reports Command Location 48 Trouble Reports Command Location 48 Trouble Reports 1 2 3 4 F 1 E 1 DefaultValues DefaultValues DefaultV...

Page 19: ...s Digit Position 2 Year 1 s Digit Position 2 Year 1 s Digit Position 2 Year 1 s Digit Position 2 Year 1 s Digit Position 2 Year 1 s Digit Position 3 Month 10 s Digit Position 3 Month 10 s Digit Posit...

Page 20: ...label into the slot on the back of the keypad base Once the installation is complete connect AC and DC power Complete programming if required Test all panel operations DS1 DS1 DS1 DS1 DS1 WATCH WATCH...

Page 21: ...Instant Home Arming Also called Instant Home Arming Also called Instant Home Arming Also called Instant Home Arming Also called Instant Home Arming Instant Arm Arms system and converts delayed zones...

Page 22: ...found at various locations throughout the programming section of the manual Question Question Question Question Question What is an Interface error 1 and how do I correct the error Answer Answer Answe...

Page 23: ...o communicate at the same time The only way to correct the problem is to disconnect one of the keypads and then re address the remaining one ensuring that the new address is not in use by any other ke...

Page 24: ...This option determines the response time of the loop itself It acts 49 50 2 Time as a buffer on the loop to minimize the possibility of fast acting sensors such as swingers or window foil producing f...

Page 25: ...the audible tone Unit Control 2F 3 Enable 4 minute Suppresses all trouble and alarm reports for a period of four Power Up minutes after power is initially applied to the panel This allows Delay the se...

Page 26: ...ot functioning properly when an intrusion or fire occurs is inadequate maintenace Your alarm system should be tested weekly to make sure all sensors are operating properly The SYS3316RF panel and keyp...

Page 27: ...er 15 User 15 User 15 User 15 Name Name Name Name Name 5 6 9 E 0 0 0 0 User 14 User 14 User 14 User 14 User 14 Name Name Name Name Name 5 5 9 E 0 0 0 0 User 13 User 13 User 13 User 13 User 13 Name Nam...

Page 28: ...ations Communications Communications Communications Formats Formats Formats Formats Formats 0 3 1 1 0 0 B 0 C 0 0 0 0 0 0 Account 1 Account 1 Account 1 Account 1 Account 1 Phone 1 1st 6 digits Phone 1...

Page 29: ...Control Control Control 1 9 0 3 E 3 0 0 Loop 3 Loop 3 Loop 3 Loop 3 Loop 3 Codes Codes Codes Codes Codes 1 8 0 2 E 2 0 0 Loop 2 Loop 2 Loop 2 Loop 2 Loop 2 Codes Codes Codes Codes Codes 1 A 0 4 E 4 0...

Page 30: ...p 1 Loop 1 Loop 1 Switches Switches Switches Switches Switches 0 1 0 0 3 2 Loop 3 Loop 3 Loop 3 Loop 3 Loop 3 Switches Switches Switches Switches Switches 0 1 0 0 3 4 Loop 5 Loop 5 Loop 5 Loop 5 Loop...

Reviews: