Shore power electrical system
WARNING! Risk of electrical shock. Do not charge the boat if the RCD (residual current
device) is out of function. Disconnect the charging cable and contact Candela.
The shore power system safely distributes power to the high-voltage battery when the boat is
connected to shore power.
A
A
B C
B
C
Galvanic isolator
The protective earth of the shore power is connected to the ground system of the boat through a
galvanic isolator, to minimize the risk of ground current and galvanic corrosion.
Charging fuse box and RCD (residual current device)
The charging fuse box contains circuit breakers for overcurrent protection, and a residual current
device (RCD). The RCD detects and prevents potential ground leakage currents that could
otherwise result in serious injury and/or fire.
A.
Charging fuse box
with RCD
B.
Galvanic isolator
C.
Charge port
(and charging cable)
Trip testing the RCD
The RCD (residual current device) is located in the charging fuse box, under the sunbed stowage
bag on the starboard side.
1. Connect the boat to shore power.
2. In the charging fuse box, identify the RCD.
3. Push the RCD test button next to the RCD switch. The RCD switch should turn off, indicating
that the RCD is functioning properly.
4. Reset the RCD switch.
WARNING! Risk of electrical shock. If the RCD switch does not turn off when pushing the
test button, there is an electrical issue. Disconnect the charging cable and contact
Candela.