C&D Technologies DCS-100HIT Maintenanse Instructions Download Page 7

Environment Ambient and

Battery Temperature

While the VRLA battery will function at extremes
of temperature, it is rated at 77°F (25°C) and the
ideal operating temperature range for the 10
Year VRLA battery is 70°F (21°C) to 80°F (27°C).
Operation at cooler temperatures will reduce the 
anticipated standby operating time while 
operation at warmer temperatures will detract
from the battery life and will increase the 
potential of a thermal runaway condition.

The battery will experience a 50% reduction of
life for each 18°F (10°C) above 77°F (25°C).
High ambient room temperature should be corrected
through the use of appropriate ventilation and air
conditioning.

The VRLA battery should not be charged at 
temperatures exceeding 122°F (50°C). A thermal
runaway condition could result.

The individual batteries within the string should
not exceed the ambient temperature by more
than 18°F (10°C). If the entire battery or individual
units temperatures are excessively high, the 
respective units may be experiencing thermal
runaway. In this situation the charging current
should be terminated by disconnecting the
Charger/Rectifier and the cause of the situation
should be determined and corrected.

If thermal runaway has occurred, the battery 
system should be capacity tested and replaced
if necessary.

Battery Visual Inspection

Container Cleanliness

It is important that the individual batteries be
clean and properly spaced. An accumulation 
of dirt or dust and moisture on the covers can 
produce a conductive path between the 
terminals or to ground which could result in 
short circuits or ground faults.

When batteries are cleaned, they should be on

open circuit. For cleaning, use a cloth moistened
in a solution of bicarbonate of soda and water. 
Do not use cleaners of unknown solutions such
as window or glass cleaners and solvents. Use of
certain petroleum based cleaners will damage the
battery plastic containers and could cause them
to crack and craze.

Container and Cover Damage

Should a crack or other penetration of the 
container or cover of a battery be noted, it should
be replaced. A crack in the container could allow
conductive electrolyte to wick from the battery and
create a ground fault. A ground fault could lead to
melting and burning of the container.

A hole in the cover, even without wicking of the
electrolyte, can also be a serious situation. 
The hole will allow drying of the electrolyte in the 
subject cell resulting in an eventual high resistance
and heating of the subject cell.

Containers which are severely swollen and
permanently deformed have been overheated and
experienced thermal runaway. Thermal runaway
will also cause the batteries to gas and dry out
and will damage the plates. In this case the entire
battery string should be replaced.

Terminals

Bent or otherwise damaged terminals can 
produce high resistance connections or can 
hide a fracture that could fuse open under load.
Batteries with damaged terminals should be 
replaced. 

If the protective grease at a termination has
melted and flowed onto the cover, it is an 
indication that the connection has been hot and
this is, in all probability, the result of a loose or
high resistance connection. In this situation the
connection should be disassembled, inspected 
for damage, cleaned and properly reassembled.

41-7546/0213/CD                                                                                            7                                                                                        www.cdtechno.com

Summary of Contents for DCS-100HIT

Page 1: ...Valve Regulated Lead Acid Battery 20 to 200 ampere hours capacity 10 Year VRLA Battery Periodic Maintenance Instructions 41 7546 TECHNICAL BULLETIN 41 7546 0213 CD www cdtechno com...

Page 2: ...and Battery Temperature 7 Battery Visual Inspection 7 System Float Voltage 8 Ground Fault Check 8 Float Charging Current 9 Individual Battery Float Voltage 9 High Rate Momentary Load Test 10 Battery...

Page 3: ...acity of the sum of the capacities of the individual strings The 10 Year VRLA battery is a lead acid battery which facilitates an oxygen recombination cycle The net result is that under normal conditi...

Page 4: ...e battery system Disposal Lead acid batteries are to be recycled Batteries contain lead and dilute sulfuric acid Dispose of in accordance with Federal State and local regulations Do not dispose of in...

Page 5: ...loat voltage 6 Momentary high rate load test 7 Battery system capacity test A test of the individual unit resistance impedance or conductance while optional is also recommended on a periodic basis Thi...

Page 6: ...atteries are functional 4 Optionally measure and record the resistance impedance conductance of the individual units to trend the condition of the individual units over time and to detect dramatic dif...

Page 7: ...n short circuits or ground faults When batteries are cleaned they should be on open circuit For cleaning use a cloth moistened in a solution of bicarbonate of soda and water Do not use cleaners of unk...

Page 8: ...ates may have occurred and the battery may have to be replaced Extended overcharging will cause excessive float current corrosion of the plate grids gassing and drying of the limited amount of electro...

Page 9: ...acteristics for each series battery as listed in the documents noted in the table of contents which lists the minimum and maximum DC float voltages to be measured across batteries in a series string I...

Page 10: ...of this data can indicate string uniform gradual degradation and loss of capacity with time This is shown in Figure 4 Rapid changes in individual units may indicate shorted open and drying cells and...

Page 11: ...replacement is when it no longer supports the load for the minimum required time even if the battery is still greater than 80 of rating However even at minimal load the battery should not remain in s...

Page 12: ...d develop thermal runaway internal arcing could result in explosion Heat the battery Run parallel cables Add required parallel strings Replace isolated units with shorts and evaluate entire string Ele...

Page 13: ...rmal runaway possibly caused by high temperature environment overcharging excessively high recharge current shorted cells or a ground fault or a combination of these items Could result in the emission...

Page 14: ...eal that is attacking the interunit connector Increased connection resistance and resulting increase in the connection heating and voltage drop at high rate discharge Disassemble connection clean coat...

Page 15: ...y Equalization and boost charging will be less effective and will require extended time If possible reset the charger output voltage to the recommended value or accept longer equalization time Individ...

Page 16: ...of the value of the DC float voltage Poor filtering of the charger output Excessive AC ripple could cause the battery to cycle at the ripple frequency and result in heating and deterioration of the p...

Page 17: ...time Fully recharge the battery AC ripple current exceeds 5 amperes per 100 Ah rated battery capacity Poor filtering of the charger Excessive AC ripple current will result in battery heating reduced...

Page 18: ...battery or replace as required Connection resistance increase of 20 or more from original value Repetitive cycles resulting in heating and cooling of connection can result in relaxation of torque and...

Page 19: ...TEL12 70 Inserted 1 4 20 110 12 84 13 5 13 8 245 9 3 8 0 0050 1326 TEL12 80 SLC Inserted 1 4 20 110 12 84 13 5 13 8 283 10 4 4 0 0040 1467 TEL12 90 Inserted 1 4 20 110 12 84 13 5 13 8 331 11 5 0 0 003...

Page 20: ...sion by C D Technologies Inc without notice While such information is believed to be accurate as indicated herein C D Technologies Inc makes no warranty and hereby disclaims all warranties express or...

Reviews: