C&D Technologies DCS-100HIT Maintenanse Instructions Download Page 6

Quarterly Maintenance

The following checks should be completed 
quarterly.

1. Assure the battery room is clean, free of

debris and well lighted.

2. Assure that all facility safety equipment is

available and functional.

3. Measure and record the air temperature

within the battery room.

4. Visually inspect the battery for:

a. cleanliness.
b. terminal damage or evidence of 

heating.

c. container or cover damage.
d. evidence of overheating

5. Measure and record the battery system

DC float charging voltage at the battery.
Optionally measure and record the AC 
ripple voltage at this time also.

6. Measure the DC voltage from each 

polarity of the battery to ground to detect
any ground faults.

7. If possible, measure and record the battery

system DC and AC float charging current.

8. Measure and record the temperature of

the battery pilot unit. Measure the 
temperature on the side of the unit in the
center or at the negative terminal of 
the unit.

9. Measure and record the individual unit 

DC float charging voltage.

10. Measure and record the System 

Equalization Voltage.

Semi-Annual Maintenance

1  Repeat the quarterly checks,
2. Optionally perform the 10 sec. high rate

(e.g. 100 amp) load test to assure the 
individual batteries are functional.

3. Optionally perform the 10 sec. high rate

(e.g. 100 amp) load test to assure the 
individual batteries are functional.

4. Optionally measure and record the 

resistance/impedance/conductance of 
the individual units to trend the condition of
the individual units over time and to detect
dramatic differences between individual
units and the norm.

Annual Maintenance

1. Repeat the semi-annual checks.
2. Retorque all the interunit connecting 

hardware to the values noted in tables
listed in the Table of Contents.
This can be omitted if the connection 
resistance is measured and found to have
not increased more than 20% from the
value at installation.

Bi-Annual Maintenance

The battery should be capacity tested every two
years at the service load or at the battery rating
related to the service requirements. Ideally, this
will be the same rate at which it was acceptance
tested when originally installed. Once the battery
is found to be at 85% of rating, it should be 
capacity tested annually. Capacity testing instructions
are found in the bulletin "Acceptance and 
Capacity Testing" #41-7135.

Data Analysis and Corrective Actions

The data accumulated during the periodic
maintenance activities should be recorded on a
form such as shown in Appendix One. Following is an
explanation of how the data would be interpreted
and the correction action to be taken. However, it
must be recognized that this explanation is not all
inclusive and the analysis and corrective action
decision must be made by personnel familiar with 10
Year VRLA batteries and their operation and 
failure modes.

41-7546/0213/CD                                                                                           6                                                                                       www.cdtechno.com

Summary of Contents for DCS-100HIT

Page 1: ...Valve Regulated Lead Acid Battery 20 to 200 ampere hours capacity 10 Year VRLA Battery Periodic Maintenance Instructions 41 7546 TECHNICAL BULLETIN 41 7546 0213 CD www cdtechno com...

Page 2: ...and Battery Temperature 7 Battery Visual Inspection 7 System Float Voltage 8 Ground Fault Check 8 Float Charging Current 9 Individual Battery Float Voltage 9 High Rate Momentary Load Test 10 Battery...

Page 3: ...acity of the sum of the capacities of the individual strings The 10 Year VRLA battery is a lead acid battery which facilitates an oxygen recombination cycle The net result is that under normal conditi...

Page 4: ...e battery system Disposal Lead acid batteries are to be recycled Batteries contain lead and dilute sulfuric acid Dispose of in accordance with Federal State and local regulations Do not dispose of in...

Page 5: ...loat voltage 6 Momentary high rate load test 7 Battery system capacity test A test of the individual unit resistance impedance or conductance while optional is also recommended on a periodic basis Thi...

Page 6: ...atteries are functional 4 Optionally measure and record the resistance impedance conductance of the individual units to trend the condition of the individual units over time and to detect dramatic dif...

Page 7: ...n short circuits or ground faults When batteries are cleaned they should be on open circuit For cleaning use a cloth moistened in a solution of bicarbonate of soda and water Do not use cleaners of unk...

Page 8: ...ates may have occurred and the battery may have to be replaced Extended overcharging will cause excessive float current corrosion of the plate grids gassing and drying of the limited amount of electro...

Page 9: ...acteristics for each series battery as listed in the documents noted in the table of contents which lists the minimum and maximum DC float voltages to be measured across batteries in a series string I...

Page 10: ...of this data can indicate string uniform gradual degradation and loss of capacity with time This is shown in Figure 4 Rapid changes in individual units may indicate shorted open and drying cells and...

Page 11: ...replacement is when it no longer supports the load for the minimum required time even if the battery is still greater than 80 of rating However even at minimal load the battery should not remain in s...

Page 12: ...d develop thermal runaway internal arcing could result in explosion Heat the battery Run parallel cables Add required parallel strings Replace isolated units with shorts and evaluate entire string Ele...

Page 13: ...rmal runaway possibly caused by high temperature environment overcharging excessively high recharge current shorted cells or a ground fault or a combination of these items Could result in the emission...

Page 14: ...eal that is attacking the interunit connector Increased connection resistance and resulting increase in the connection heating and voltage drop at high rate discharge Disassemble connection clean coat...

Page 15: ...y Equalization and boost charging will be less effective and will require extended time If possible reset the charger output voltage to the recommended value or accept longer equalization time Individ...

Page 16: ...of the value of the DC float voltage Poor filtering of the charger output Excessive AC ripple could cause the battery to cycle at the ripple frequency and result in heating and deterioration of the p...

Page 17: ...time Fully recharge the battery AC ripple current exceeds 5 amperes per 100 Ah rated battery capacity Poor filtering of the charger Excessive AC ripple current will result in battery heating reduced...

Page 18: ...battery or replace as required Connection resistance increase of 20 or more from original value Repetitive cycles resulting in heating and cooling of connection can result in relaxation of torque and...

Page 19: ...TEL12 70 Inserted 1 4 20 110 12 84 13 5 13 8 245 9 3 8 0 0050 1326 TEL12 80 SLC Inserted 1 4 20 110 12 84 13 5 13 8 283 10 4 4 0 0040 1467 TEL12 90 Inserted 1 4 20 110 12 84 13 5 13 8 331 11 5 0 0 003...

Page 20: ...sion by C D Technologies Inc without notice While such information is believed to be accurate as indicated herein C D Technologies Inc makes no warranty and hereby disclaims all warranties express or...

Reviews: