background image

BNT95 Series Valve Operation Manual                                         

 

- 27 -       

                                             

General Valve Installation                                                                                 

 

Water Pressure 

Minimum 25 PSI 

Electrical Supply 

Uninterrupted AC 

Existing Plumbing 

Free of any deposits or built-ups inside pipes 

Softener Location 

Locate close to drain and connect according to 

plumbing codes 

Bypass Valves 

Always provide for bypass valve if unit is not 

equipped with one 

 

CAUTION 

„

 

Do not exceed 120 psi water pressure.

 

„

 

Do not exceed 110

water temperature.

 

„

 

Do not subject unit to freezing conditions

.

 

 

1.  Locate the softener tank and brine tank close to a drain where the system will be installed. 

The surface should be clean and level. 

2.  Perform all plumbing according to local plumbing codes. 
              Use a 1/2” minimum pipe or tubing size for the drain line. 
       Use a 3/4” pipe or tubing for backwash flow rates that exceed 7 gpm or length that 

exceeds 20ft (6m). 

3.  Only use Teflon tape on the drain fitting. Any solder joints near the valve must be done before 

connecting any piping to the valve. Always leave at least 6” (152 mm) between the valve and 
joints when soldering pipes that are connected to the valve. Failure to do this could cause 
damage to the valve. 

4.  Cut the 1” central pipe flush with top of each tank. 
5.  Lubricate the o-ring on the bottom of valve that seals against the tank. Screw the valve on to 

the tank. Be careful to not cross thread the valve into the tank. Only use silicone lubricant.   

6.  Add water until there is approximately 1” (25mm) of water above the grid plate. If the tank 

does not have a grid, add water until it is above the air check in the brine tank. Do not add salt 
to the brine tank at this time. 

7.  If the unit has a bypass valve, place it in the bypass position. 
8.  Slowly turn on the main water supply. 
9.  Open a cold soft water tap nearby and let water run a few minutes or until the system is free 

of foreign material resulting from the plumbing work. Close the water tap when water runs 
clean. 

10. Place the bypass in the service position and let water flow into the mineral tank. When water 

flow stops, slowly open a cold water tap nearby and let water run until air is purged from the 
unit. Then close tap. 

 

 

 

 

 

Summary of Contents for BNT95 Series

Page 1: ...s 5 6 Default Settings 7 Manual Regeneration 7 Water Hardness Adjustment Optional for Softener Valve 7 Optional Parts 8 1 Inlet Outlet Screw Standards 8 2 Inlet Outlet Screw Adaptor Optional 8 3 Inlet Outlet Connections Types 9 4 Drain Line Flow Controls DLFC and Injector 10 5 Bypass Assembly 11 Valve Powerhead Assembly 12 Valve Body Assembly 14 Bypass Assembly 17 General Valve Installation 19 Tro...

Page 2: ... information including volume remaining flow rate meter mode regeneration days remaining timer mode BNT95 Series Outline BNT95 Button Pad Main Functions Valve Operation Mode 1 SOFTENER Standard water softener operation 2 FILTER Automatic backwashing filters such as Multi Media Depth or Carbon Filter Regeneration Mode 1 Calendar Clock 2 METER IMMEDIATE 3 METER DELAYED 4 Meter Override Holiday Mode ...

Page 3: ... minutes during the stand by status Press and hold MENU button for 3 seconds to unlock Specifications Hydrostatic Test Pressure 350 psi 24 15 bar Working Pressure 20 125 psi 1 38 8 62 bar Working Temperature 1 39 Riser Pipe Diameter Required 1 05 OD with 2 5 Valve Base 2 OD with 4 Valve Base Electrical Adapter Input AC110V AC240V 50Hz 60Hz Output AC12V Pressure Tank Thread 2 5 NPSM or 4 NPSM Inlet...

Page 4: ... Press the or button to select a parameter Press the SET REGEN button the parameter starts flashing Press the or button to change the value Press the SET REGEN button to save the setting Press the or button to select other parameters Follow the above steps to change other parameters Press the MENU button to exit settings You can only change the flashing parameters Program will be back to standby s...

Page 5: ...Capacity Remaining of next regeneration and current Flow Rate Numbers of blue bar represent the Remaining Days at Calendar Clock mode Numbers of blue bar represent the Capacity Remaining the Flow Rate at Meter Mode Screen will be locked if any button without being operated at the standby display 4 System Initialization When power is first supplied the valve may take about two minutes to initialize...

Page 6: ...ndby display 5 Manual Regeneration Press and hold the SET REGEN button for 3 seconds to initiate a manual regeneration and screen will display When the valve reaches Backwash position screen will display When Backwash Remaining time reaches zero or any button is operated valve will be advanced to next cycle position Brine and screen will display ...

Page 7: ...ress the or button to move the cursor to the desired setting item Press the SET REGEN button to enter the setting item Current date and current time setting Current date and current time can be set in Time setting item Setting method Press the or button to move the cursor to the desired parameter Press the SET REGEN button to let the parameter flashing Press the or button to change the value Press...

Page 8: ...ing Unit format can be selected in Region setting item Setting method Press the or button to move the cursor to the desired parameter Press the SET REGEN button to confirm and save the setting and display returns to main page Language setting Language can be selected in Language setting item Setting method is as the Region item setting ...

Page 9: ...e end of date of holiday to let the valve clean the media during your holiday Once you turn on the Holiday Mode the valve s regeneration only has two cycles Backwash and Rinse Advanced Settings is as the follows Regeneration Days Backwash duration and Rinse duration can be set to control regeneration cycles of holiday Advanced Settings ...

Page 10: ...s item The key regeneration parameters Capacity Refill Time etc can be calculated in the Automatic Calculate mode Automatic Calculate mode s page under different regeneration mode is as follows Calendar Clock Meter Immediate Meter Delayed Meter Override Manual Settings mode s page under different regeneration mode is as follows ...

Page 11: ...eration days Meter Immediate the unit will initiate regeneration immediately after the volume remaining reaches zero Meter Delayed this is the most common setting When the volume remaining reaches zero the system will initiate regeneration at the next preset regeneration time Meter Override when the volume remaining reaches zero the system will initiate regeneration at the next pre set regeneratio...

Page 12: ...time of day when regeneration will start Regen Days This value is the interval days between regenerations It is used to determine how many days between regenerations Water Usage This setting is used to calculate the interval days between regenerations Monthly Water Usage is the water usage of average of months ...

Page 13: ...and out to the drain Brine time controls the length of time for the unit to draw regeneration brine for softeners from the brine tank and slowly rinse the media tank from the top to the bottom Rinse time controls the length of time to give the tank a final rinse from the top to the bottom in order to remove any last traces of the regeneration from the tank Refill time controls the length of time w...

Page 14: ...lated under Automatic Calculate mode Restore Defaults This setting allows the current settings to be erased and changed back to the default settings System Information Press the or button to inquire some information of valve by entering System Information item ...

Page 15: ...BNT95 Series Valve Operation Manual 14 In Total Regenerations and Peak Flow Rate page press and hold SET REGEN button for 3 seconds can reset the value to zero ...

Page 16: ...t Cam Hole turn the Cam anti clockwise to the marked position Remove the Connector Remove the Locking Bar Pull outward the Controller Assembly Automatic removing the Controller Assembly Unlock the screen Press and hold button the valve will advance the Cam to the marked position Remove the Connector Remove the Locking Bar Pull outward the Controller Assembly ...

Page 17: ...l To replace the Drain Line Flow Control DLFC Remove the Clip Pull the Drainlet outward Pull the DLFC Holder outward from the Drainlet Replace the DLFC To replace the Brain Line Flow Control BLFC Remove the Clip Pull the Brinelet outward Pull the BLFC Holder outward from the Brinelet Replace the BLFC ...

Page 18: ...the Injector Body and Injector Cover outward Slightly pull out the Screen Replace the Nozzle Slightly pull out the Air Disperser Replace the Throat Injectors DLFC and BLFC s Suggest Configuration with Tanks Softener Filter 10 1 1 01 03 12 2 1 02 1 14 5 1 03 2 16 6 2 1 3 18 6 2 2 4 21 7 3 3 5 24 7 3 4 6 Tank Size inch BLFC DLFC Injector ...

Page 19: ...040009 Bnt95 Driven Cam 1 A08 05010078 Magnet Ø4x3 1 A09 05040095 Bnt95 Brine Valve Connector 1 A10 05056085 Screw ST2 9 10 Large Wafer 7 A11 05040052 Bnt95 Sensor Pcb 1 A12 05010047 Friction Point 6 A13 05040007 Bnt95 Mounting Plate 1 A14 05056084 Screw ST3 5 13 10 A15 05056129 O Ring Ø23 3 1 A16 05040054 Bnt95 Meter Cable 1 05040039 Bnt95 Meter Cover 1 05040037 Bnt95 Cable Jaket with hole 1 0504...

Page 20: ...1 A23 05040033 Bnt95 Piston Rod Bush 1 A24 05040041 Bnt95 Manual Button 1 A25 05040085 O Ring Ø10 2 5 1 A26 05040051 Bnt95 Main PCB 1 A27 05056529 Bnt465 Button 4 A28 05040043 Bnt95 Housing Seal 1 A29 05040036 Bnt95 Clear Cover 1 A30 05040006 Bnt95 Cover 1 A31 05040092 Bnt95 Label Filter 1 05040093 Bnt95 Label Softener 1 A32 05040026 Bnt95 Brine Valve Piston Rod 1 ...

Page 21: ...029 Bnt95 Quad Ring Holder 2 B03 05040004 Bnt95 End Plug Retainer 1 B04 05040024 Bnt95 Piston Rod Holder 1 B05 05040022 Bnt95 Spacer Seal 5 B06 05040002 Bnt95 Valve Boby 1 05040049 Bnt95 Nut M6 6 05056101 Nut M5 6 B07 05040069 Bnt95 DLFC 1 1 05040070 Bnt95 DLFC 2 1 05040071 Bnt95 DLFC 3 1 05040072 Bnt95 DLFC 4 1 05040073 Bnt95 DLFC 5 1 05040074 Bnt95 DLFC 6 1 05040075 Bnt95 DLFC 7 1 B08 05040030 B...

Page 22: ...Nozzle 2 1 05040059 Bnt95 Nozzle 3 1 05040061 Bnt95 Nozzle 4 1 05040063 Bnt95 Nozzle 5 1 05040065 Bnt95 Nozzle 6 1 05040067 Bnt95 Nozzle 7 1 B25 05040099 Screw M5 55 Hexagon with Washer 2 B26 05040011 Bnt95 Injector Cover 1 B27 05040048 Bnt95 Brine Valve Screen 1 B28 05040027 Bnt95 Brine Valve Spacer 1 B29 05040028 Bnt95 Brine Valve Seal Cover 1 B30 05040050 Bnt95 Brine Valve Rod Pin 1 B31 0505607...

Page 23: ...74 5 33 1 B39 26010103 O Ring Ø25 3 55 1 B40 05040001 Bnt95 Valveset 2 5inch 1 B41 O Ring Ø108 5 3 1 B42 05040091 Bnt95 Seal Holder 1 B43 05040088 Screw M6 30 Hexagon with Washer 6 B44 05040090 Bnt95 Valveset 4inch 1 B45 05040082 O Ring Ø47 3 2 B46 05040003 Bnt95 Spacer 10 B47 05040021 Bnt95 Piston 1 B48 05040016 Bnt95 Housing Locking Bar 2 B49 05056088 Screw M5 16 Hexagon with Washer 4 ...

Page 24: ... 10 00 20 00 30 00 40 00 50 00 60 00 70 00 80 00 90 00 0 00 10 00 20 00 30 00 40 00 50 00 60 00 Service Flow Rate GPM Pressure psi 0 0 10 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 0 0 00 10 00 20 00 30 00 40 00 50 00 60 00 Service Flow Rate GPM Pressure Drop psi ...

Page 25: ...jector 2 0 00 25 00 50 00 75 00 100 00 125 00 0 00 0 50 1 00 1 50 2 00 2 50 3 00 3 50 Brine Flow Rate GPM Pressure psi 0 00 25 00 50 00 75 00 100 00 125 00 0 00 0 50 1 00 1 50 2 00 2 50 3 00 3 50 Brine Flow Rate GPM Pressure psi Injector 3 Injector 4 0 00 25 00 50 00 75 00 100 00 125 00 0 00 0 50 1 00 1 50 2 00 2 50 3 00 3 50 Brine Flow Rate GPM Pressure psi 0 00 25 00 50 00 75 00 100 00 125 00 0 ...

Page 26: ...i DLFC 1 DLFC 2 0 00 20 00 40 00 60 00 80 00 100 00 120 00 140 00 0 00 10 00 20 00 30 00 40 00 Backwash Flow Rate GPM Pressure psi 0 00 20 00 40 00 60 00 80 00 100 00 120 00 140 00 0 00 10 00 20 00 30 00 40 00 Backwash Flow Rate GPM Pressure psi DLFC 3 DLFC 4 0 00 20 00 40 00 60 00 80 00 100 00 120 00 140 00 0 00 10 00 20 00 30 00 40 00 Backwash Flow Rate GPM Pressure psi 0 00 20 00 40 00 60 00 80...

Page 27: ...BLFC 1 BLFC 2 0 00 20 00 40 00 60 00 80 00 100 00 120 00 140 00 0 00 2 00 4 00 6 00 8 00 10 00 Backwash Flow Rate GPM Pressure psi 0 00 20 00 40 00 60 00 80 00 100 00 120 00 140 00 0 00 2 00 4 00 6 00 8 00 10 00 Backwash Flow Rate GPM Pressure psi BLFC 3 BLFC 4 0 00 20 00 40 00 60 00 80 00 100 00 120 00 140 00 0 00 2 00 4 00 6 00 8 00 10 00 Backwash Flow Rate GPM Pressure psi 0 00 20 00 40 00 60 0...

Page 28: ...g to the valve Always leave at least 6 152 mm between the valve and joints when soldering pipes that are connected to the valve Failure to do this could cause damage to the valve 4 Cut the 1 central pipe flush with top of each tank 5 Lubricate the o ring on the bottom of valve that seals against the tank Screw the valve on to the tank Be careful to not cross thread the valve into the tank Only use...

Page 29: ...pes 2 Iron build up inside valve or tank Clean control and add resin cleaner to clean bed Increase regeneration frequency D Low water pressure 3 Inlet of control plugged due to foreign material Remove piston and clean control valve 1 Air in water system Check well system for proper air eliminator control E Resin in drain line 2 Incorrect drain line flow control DLFC button Check for proper flow ra...

Reviews: