1.

A qualified electrician in accordance with all local and National Electrical Codes should do all wiring.  

2.

Ensure power supply is disconnected and locked out prior to making electrical connections.   

3.

Wire the motor according to the wiring diagram on motor label or on the sticker inside the motor wrap. All motors should be wired to 

the same rotation as indicated on the sticker on the top plate.  

4.

Leave enough slack in the wiring to allow for motor movement when adjusting the belt tension.   

5.

Excess wire must be restrained in order to prevent it from entering the pulley, shaft or wheel rotating area.   

6.

Disconnect switches are recommended and should be located near the fan in order to, swiftly cut off power in case of an emergency 

and maintain complete control of the power source.

Some single phase direct drive motor’s running RPM can be adjustable with a variable speed control (please contact factory for more  

information). The speed control knob starts at off position, then high to low adjust range. At high speed, the speed control would allow the 

motor running at its maximum RPM. Dial the knob to the low side would let the speed control regulate the voltage on the motor to reduce 

the RPM. 
A minimum speed adjustment is needed to limit the motor RPM range. Follow this procedure to set the minimum speed. 

1.

Motor must be in servicing status to allow the minimum speed setting. Motor would not slow down unless proper load is applied.   
Motor RPM would be changed under different system (static pressure). 

2.

Turn the main control knob to the lowest speed position. 

3.

Locate and adjust the minimum speed setting, it can be found on the control box itself. 

4.

Motor RPM range would be from full RPM to the RPM just set.  

 

The lowest minimum voltage that may be applied to the motors is 65VAC. Running at lower voltage can cause premature failure 

to the motor.

 

For 3 phase motors, a variable frequency drive (VFD) is required to adjust motor speed.

VARIABLE SPEED CONTROL – SINGLE PHASE

VARIABLE FREQUENCY DRIVE – THREE PHASE

INSTALLATION

RECOMMENDED
ROOF OPENING

WIRED TO POWER

BY OTHERS

ROOF

DECK

OPTIONAL DISCONNECT CAN 

BE MOUNTED INSIDE THE 

HOUSING OR OUTSIDE

MINIMUM 12”

RECOMMENDED
ROOF OPENING

ROOF

DECK

MINIMUM 12”

WIRE OPTION 2:

WIRE THROUGH

THE VENT TUBE

WIRE OPTION 1:

THROUGH CONDUIT

GENERAL CLEAN AIR APPLICATION (UPBLAST)

GENERAL CLEAN AIR APPLICATION, DOWNBLAST

Note: ALX105 to ALX120 has only wiring option 1, ALX135 to ALX180 has both 

wiring options 1 and 2, ALX210 and larger has only wiring option 2.

STANDARD WIRING INSTRUCTIONS

1.

Install roof curb, caulk and flash to ensure the water tightness. 

2.

Rotate the blower wheel by hand. Wheel should not be rubbing against the housing inlet. If rubbing occurs, loosen the set screws on 

the wheel hub and shift the wheel to obtain clearance. Then re-tighten all set screws. 

3.

Complete all subsequent duct connections. 

4.

Secure the fan to the curb cap. Do not lift the unit by the hood or motor. Lift the unit by horizontal supports on direct drive or by motor 

mounting plate for belt drive unit. 

5.

Use at least 8 proper fasteners to connect the blower base to the roof curb. 

6.

Verify if the power supply is compatible with the equipment.  

7.

Make sure the power line is shut down before wiring the motor to power line. 

8.

Remove top cap, connect power line to the motor/disconnect switch as indicated. 

9.

For all up blast units, the electrical supply enters the motor compartment through the vent tube. 

10.

Ensure all fasteners and set screws are tightened. 

11.

Place the top cap back on the hood. 

12.

Caulk and flash the fan base including the fan base corners and roof curb to ensure good water tightness. 

Summary of Contents for ALX105-UD

Page 1: ... LADING AND FILE A CLAIM IMMEDIATELY WITH THE FREIGHT COMPANY DO NOT LIFT THE UNIT BY THE HOOD OR MOTOR PLEASE LIFT THE UNIT BY HORIZONTAL SUPPORTS DIMENSION COMPONENT ALX M 06_27_22 Page 1 of 7 A B D E C G F A B D E C G F UPBLAST MODELS DOWNBLAST MODELS NOTE DUE TO MOTOR MANUFACTURERS VARIANCES IN DESIGN PLEASE SEE PAGE 5 FOR MOTOR DIMENSIONAL GUIDELINES DOWNBLAST UPBLAST Downblast Direct Drive S...

Page 2: ... from full RPM to the RPM just set The lowest minimum voltage that may be applied to the motors is 65VAC Running at lower voltage can cause premature failure to the motor For 3 phase motors a variable frequency drive VFD is required to adjust motor speed VARIABLE SPEED CONTROL SINGLE PHASE VARIABLE FREQUENCY DRIVE THREE PHASE INSTALLATION RECOMMENDED ROOF OPENING WIRED TO POWER BY OTHERS ROOF DECK...

Page 3: ...odel The control module features a 4 digit LED display that indicates demand of full speed and motor speed in rpm The display also indicates an error code message for minor diagnostics if required Motor speed can be changed by adjusting the speed control pot located on the control module A small screwdriver can be used to make the speed adjustment ALX SERIES SPUN ALUMINUM EXHAUSTERS ALX M 06_27_22...

Page 4: ...s can be used in the system RESTAURANT EXHAUST APPLICATION 1 Lock out all power sources 2 Inspect all fasteners and set screws and tighten as required 3 Inspect belt alignment and tension where applicable 4 Confirm power source voltage and motor voltage are the same and that the motor is wired correctly 5 Rotate the wheel to ensure that neither the fan blade nor the belts come into contact with th...

Page 5: ...lippage which will burn out belts Proper belt deflection should be 1 64 half way between sheave centers for each inch of belt span when a force of approximately 5 lbs is applied 6 The belt alignment should be checked to be sure that the belt is running perpendicular to the rotating shafts Motor and drive shafts must be parallel 7 A periodic inspection of all fasteners should be carried out to ensu...

Page 6: ...7 NO 5 5 ALX180UB DB 48 56 143 145 8 5 8 13 7 NO 5 5 ALX210UB DB 56 143 145 182 184 11 5 11 12 8 YES 8 ALX245UB DB 56 143 145 182 184 11 5 11 12 8 YES 8 FAN MAX A MAX B MAX C C FACE ONLY ALX105 120UD 14 14 8 5 56 FRAME ALX105 120DD 10 10 7 5 56 FRAME ALX135 150UD 15 15 15 56 FRAME ALX135 150DD 15 15 15 56 FRAME ALX165UD 16 16 15 5 56 FRAME ALX165DD 16 16 15 5 56 FRAME 1 HP ADAPTER PLATE 48 OR 56 F...

Page 7: ...ary according to size ALX M 06_27_22 Page 7 of 7 Canarm Ltd Corporate Head Office 2157 Parkedale Avenue PO Box 367 Brockville Ontario Canada K6V 5V6 Tel 613 342 5424 Fax 613 342 8437 www canarm com hvacsales canarm ca WARRANTY CANARM Ltd warrants every new fan to be free of defects in material and workmanship to the extent that within a period of one year from the date of purchase CANARM Ltd shall...

Page 8: ...T FAIRE UNE RÉCLAMATION AU TRANSPORTEUR IMMÉDIATEMENT NE SOULEVEZ PAS L ÉQUIPEMENT PAR LE CAPOT OU LE MOTEUR SOULEVEZ L UNITÉ PAR LES SUPPORTS HORIZONTAUX DIMENSIONS ET PIÈCES ALX M FR 06_27_22 Page 1 de 7 MODÈLE À DÉBIT VERS LE HAUT MODÈLE À DÉBIT VERS LE BAS MODÈLE À DÉBIT VERS LE HAUT MODÈLE À DÉBIT VERS LE BAS Modèle A B C D E F G Ø Diamètre de la roue Ouverture Toit Poids Net LBS ALX105 UD 17...

Page 9: ...er un défaillance prématurée du moteur Pour un moteur 3 phases un entraînement à fréquence varaible VFD est requis pour ajuster la vitesse du moteur CONTRÔLE DE VITESSE VARIABLE UNE PHASE ENTRAÎNEMENT À FRÉQUENCE VARIABLE TROIS PHASES 1 Posez le rebord le scellant et la membrane pour assurer l étanchéité 2 Tournez la roue du souffleur à la main La roue ne doit pas frotter contre le boîtier Si il y...

Page 10: ...ire La vitesse du moteur peut être changée en ajustant le pot de contrôle de la vitesse situé sur le module de contrôle Un petit tournevis peut être utilisé pour faire cet ajustement Contrôle de la Vitesse de Moteur EC Contrôlé électroniquement N B Les moteurs EC ont un démarrage progressif À la mise sous tension le module de commande recueille les informations sur le moteur puis commence le proce...

Page 11: ... attaches sont serrées et que la tension des courries sont adéquate et bien alignées DÉMARRAGE INSTALLATION DE L ÉVACUATEUR DE RESTAURANT UL762 À DÉBIT VERS LE HAUT INSTALLATION DE L ÉVACUATEUR MURAL DE RESTAURANT À DÉBIT VERS LE HAUT OUVERTURE DU TOIT RECOMMANDÉE OUVERTURE DU TOIT RECOMMANDÉE CONDUIT SOUDÉ PAR AUTRUI CONDUIT SOUDÉ PAR AUTRUI REBORD VENTILÉ MINIMUM DE 20 DE LA CIME DU TOIT CÂBLÉ P...

Page 12: ... qui pourraient endommager la courroie 5 La tension adéquate de la courroie est importante Trop serrée cause une pression excessive sur les roulement à billes qui pourrait résulter en une surcharge du moteur Une courroie trop lâche résulte en un glissement de la courroie qui la brûlera La déflection adéquate de la courroie est à 1 64 à demi distance des centres de poulie par pouce de longueur de c...

Page 13: ... 5 8 13 7 NO 5 5 ALX210UB DB 56 143 145 182 184 11 5 11 12 8 YES 8 ALX245UB DB 56 143 145 182 184 11 5 11 12 8 YES 8 VENTILATEUR MAX A MAX B MAX C C FACE SEULEMENT ALX105 120UD 14 14 8 5 56 FRAME ALX105 120DD 10 10 7 5 56 FRAME ALX135 150UD 15 15 15 56 FRAME ALX135 150DD 15 15 15 56 FRAME ALX165UD 16 16 15 5 56 FRAME ALX165DD 16 16 15 5 56 FRAME 1 HP ADAPTER PLATE 48 OR 56 FRAME BOTH SIDES 48 56 1...

Page 14: ...on inadéquate et non conforme aux instructions AVIS Aucune réclamation ne sera honorée par Canarm sans autorisation obtenue au préalable 1 1 1 2 3 4 4 6 5 7 8 9 4 1 2 12 4 0 1 1 3 1 ÉVACUATEUR DE LA SÉRIE ALX EN ALUMINIUM REPOUSSÉ À DÉBIT VERS LE HAUT VUE DÉTAILLÉE ITEM DESCRIPTION QTÉ 1 CAPUCHON DU HAUT 1 2 ENVELOPPE DU MOTEUR 1 3 PLAQUE SOUTIEN DE MOTEUR 1 4 ÉLIMINATEUR DE VIBRATION 4 5 PLAQUE D...

Reviews: