9 Commissioning Inverter
19 / 32
The allowed range for Australia Region A, B, C.
Region
Default value
Vv1
Vv2
Vv3
Vv4
Australia A
Voltage
207 V
220 V
240 V
258 V
Inverter reactive power level
(Q)% of S
rated
44% supplying
0%
0%
60% absorbing
Australia B
Voltage
205 V
220 V
235 V
255 V
Inverter reactive power level
(Q)% of S
rated
30% supplying
0%
0%
40% absorbing
Australia C
Voltage
215 V
230 V
240 V
244 V
Inverter reactive power level
(Q)% of S
rated
44% supplying
0%
0%
60% absorbing
Allowed
Range
Voltage
180 V to 230 V
180 V to 230 V
230 V to 265 V
230 V to 265 V
Inverter reactive power level
(Q)% of S
rated
30 to 60%
supplying
0%
0%
30 to 60%
supplying
NOTE 1 Inverters may operate at a reactive power level with a range up to 100% supplying or absorbing.
NOTE 2 Australia C parameter set is intended for application in isolated or remote power systems.
3) Set protection parameters (overvoltage and under frequency) according to the local requirement.
Notice: Change the parameters under off-grid mode only.
FIG. 9-9 Set Protection Parameters