8. Troubleshooting
NOTE:
If the inverter displays any alarm message as listed in Table 8.1; please
turn off the inverter (refer to Section 5.2 to stop your inverter) and wait for 15
minutes before restarting it (refer to Section 5.1 to start your inverter). If the
failure persists, please contact your local distributor or the service center.
Please keep ready with you the following information before contacting us.
1. Serial number of Canadian Solar Three Phase Inverter;
2. The distributor/dealer of Canadian Solar Three Phase Inverter (if available);
3. Installation date.
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
of the LED status indicator lights. Other readings obtained from the Information submenu
(refer to Section 6.2) will also be helpful.);
5. The PV array configuration (e.g. number of panels, capacity of panels, number of strings, etc.);
6. Your contact details.
Alarm Message
Failure description
Solution
INI-FAULT
Initialization system fault
1.Restart inverter or contact installer.
12Power-FAULT
12V power supply fault
DSP-B-FAULT
Comm. failure between
main and slave DSP
Table 8.1 Fault message and description
Screen OFF
with DC applied
Inverter internally damaged
1.Do not turn off the DC switches as it will
damage the inverter.
2.Please wait for the solar irradiance reduces
and confirm the string current is less than
0.5A with a clip-on ammeter and then turn
off the DC switches.
3.Please note that any damages due to wrong
operations are not covered in the device
warranty.
Model
9. Specifications
Dimensions (W*H*D)
Weight
942*733*311 (mm)
84kg
3/PE~600
Max. DC input voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
MPPT number/Max input strings number
Rated grid voltage (Volts)
Max. output current (Amps)
Power Factor (at rated output power)
Max.efficiency
EU efficiency
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Noise emission
Cooling concept
Max.operation altitude
AC connection
Compliance
DC connection
1500
150
300
1/1
>
0.99 (0.8 leading - 0.8 lagging)
50/60
45-55 / 55-65
99.1%
98.6%
Transformerless
<
3W (without anti-PID)
-25
℃
...+60
℃
0~100%
IP65
≤
65dB(A)
Intelligent redundant cooling
13120ft / 4000m
Display
Communication connections
Warranty
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
OT Terminal connectors(Max.185mm²)
LCD, 2x20 Z
RS485, Ethernet, Optional: PLC
5 years (Extend to 20 years)
950
125000
125000
125000
120
THDi (at rated output power)
<3%
Start-up voltage (Volts)
Max short circuit input current (Amps)
Rated DC voltage (Volts)
Rated grid frequency (Hertz)
Grid frequency range (Hertz)
860...1450
900
NBR 16149-2013
NBR 16150-2013 , EN 50549-1/-2 , IEC61727
OT Terminal connectors(Max.185mm²)
IEC 62109-1/-2 , IEC62116 &EN 61000-6-2/-4
Safty/EMC standard
CSI-125-T600GL02-E