37
Display
Parameter
Name
Parameter Description
Parameter Range
Modulation
Real-time modulating output
percentage
0 to 100%
Total Run
Time Since
Installation
Monitors the amount of
operational time since the
MicoFlame was installed. The
first two digits are the number of
thousands of hours and the three
digit display shows the number of
hundreds of hours.
Press
simultaneously to
reset the counter
Alternates between
00 and 999
18.9
MODE 6 & 7: EXTERNAL TARGET TEMPERATURE INPUT OPERATION: ADJUST DISPLAY
From the Home display;
1) Press
simultaneously to view the following parameters:
Display
Parameter
Name
Parameter Description
Parameter Range
Mode
Operating mode for the boiler.
NOTE: A complete description of
each mode can be found in
section 8.4 Modes of Operation in
this manual.
1 to 8
Default = 1
Differential
Temperature
To provide a modulation rate
above and below the Boiler
Target temperature. For example,
if the value is 10
o
F and the Boiler
Target is 160
o
F the boiler will
begin to modulate at 155
o
F and
shut off at 165
o
F.
Au, 2 to 42
o
F
(Au, -17 to 6
o
C)
Default = Au
Pump Delay
Boiler post pump time after
burner has shut off, in seconds.
OFF, 0:20 to 9:55
min, On
Default = 1:00 min
Temperature
Units
Select the desired unit of
measurement
o
F,
o
C
Default =
o
F