Instantaneous DHW with Brazed Plate Heat Exchanger (combination models)
Description
Electrical Connection(s)
Programming Instructions
•
Boiler operates at a fixed
DHW setpoint
•
Modulates on boiler inlet
sensor (default)
•
Heat demand is generated
when Remote Operator is
closed.
DHW Sensor, if required.
1)
Place both toggle switches in
LOCAL
2)
Press
and select
Login
3)
Select
Advanced Setup
4)
Select
DHW Config
5)
Select
Demand switch = Plate Heat Exch,
and Press
6)
Select
Mod sensor = DHW
7)
Select
DHW Setpoint,
, and enter desired setpoint using 5-way control
8)
Place right hand toggle switch setting to
REMOTE
for remote operation (if
required)