37
The following steps are performed at the factory and verifying on site will
be sufficient:
15)
Select
Pump Configuration
16)
Press
[Advanced Options >>]
17)
Press the to arrive at
Central Heat Pump
or
DHW Pump
18)
On Options: Local burner demand
19)
On Options: Local Lead Lag Service Active
20)
Force On: Outlet high limit
Slave Boiler
Description
Electrical Connection(s)
Programming Instructions
•
Slave boiler lead lag setup
1)
Press
and
2)
Select
System Identification & Access
3)
Verify
Modbus address
. To be in sequential order
4)
Select
Lead Lag Slave Configuration
5)
Select
Slave Enabled = Enable slave for built-in Lead Lag master