26
Figure 24: Lockout Condition
To eliminate the lockout error,
1) Press the red bar, indicating a Lockout condition
2) Press the [Lockouts] button
Figure 25: Lockout History
3) Press [Clear Lockout]
Table 14: Alert/Hold Codes
#
Description
29
Burner switch turned OFF
30
Burner switch turned ON
47
Invalid subsystem reset request occurred
61
Anti-short Cycle
62
Fan speed not proved
63
LCI off, safety circuit is open
68
Setpoint was overridden due to sensor fault
69
Modulation was overridden due to sensor fault
123
Modulation rate was limited due to outlet limit
124
Modulation rate was limited due to Delta-T limit
215
No Lead Lag slaves available to service demand
219
Using backup Lead Lag header sensor due to
sensor failure
229
Lead lag slave communication timeout.
275-
281
LCI off, safety circuit is open
-
Thermal Disc in control box and/or upper
cabinet
-
Flow Switch
-
LWCO
-
Blocked Flue Switch
283
Demand off during measured purge time
291
Abnormal Recycle: Flame was not on at end of
Ignition period
292
Abnormal Recycle: Flame was lost during Main
Flame Establishing Period
293
Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
303-
310
+
Interlock Off, safety circuit is open
-
Air Inlet Damper end switch
-
High Limit (Automatic/Manual)
-
Gas Pressure Switch (Low/High)
-
Low Air Proving Switch
324,
374-
379
Hardware flame bias. Flame sensor wire needs to
be re-routed.
352
+
Stack sensor fault
355
+
Outlet sensor fault
357
+
DHW sensor fault
359
+
Inlet sensor fault
460
LCI lost in run
550
Delta T inlet/outlet limit was exceeded
* If an internal hardware fault is detected contact Camus®
technical support for troubleshooting procedure.
+
The alarm LED and alarm contacts are closed and will
remain closed until the ‘RESET’ button is pressed.