Mounting Instructions 

Follow the above mounting restrictions to allow maximum lifetime of the product and to prevent from tripping the 
internal temperature protection fuse. The ESB101 is an active device. The distance between an ESB101 and the next 
active or temperature sensitive device shall be 17,5mm or larger. The power consumption of the device is constant at 
continuous operation (2,2W @ 115Vac / 1,1W @ 230Vac). Make sure that the ventilation holes below and above the 
unit are not blocked to allow free air convection. 

Operation 
Temperature 

 Ambient 
Temperature 

 ESB101, 115Vac,  AC 16A current 

 ANSI / UL 508 

-40°C … +55°C 

 CAN / CSA C22.2 

-40°C … +55°C 

 IEC EN62368-1 / IEC EN60950-1 

-40°C … +60°C 

 ESB101, 230Vac,  AC 10A current 

 ANSI / UL 508 

-40°C … +55°C 

 CAN / CSA C22.2 

-40°C … +55°C 

 IEC EN62368-1 / IEC EN60950-1 

-40°C … +60°C 

 ESB101, 230Vac,  AC 16A current 

 ANSI / UL 508 

-40°C … +50°C 

 CAN / CSA C22.2 

-40°C … +50°C 

 IEC EN62368-1 / IEC EN60950-1 

-40°C … +55°C 

 

Table of the standards 

Product Code 

Camtec Article No. 

IEC / EN 62368-1 
IEC / EN 60950-1 

ANSI / UL508 listed 
UL-File E485106 

CAN / CSA 22.2 listed 
UL-File E485106 

GHOST EAC #0658490 
RU C-DE.MO10.B.02970 

ESB101.16(R2) 

3041081001CA 

Yes 

Yes 

Yes 

Yes 

ESB101.23S(R2) 

3041081002CA 

Yes 

Yes 

Yes 

Yes 

ESB101.23(R2) 

3041081003CA 

Yes 

Yes 

Yes 

Yes 

ESB101.33(R2) 

3041081004CA 

Yes 

Yes 

Yes 

Yes 

ESB101.LED.230VAC(R2) 

3041081005CA 

Yes 

Yes 

Yes 

Yes 

ESB101.LED.115VAC(R2) 

3041081006CA 

Yes 

Yes 

Yes 

Yes 

ESB101.23S.115VAC(R2) 

3041081007CA 

Yes 

Yes 

Yes 

Yes 

ESB101.05UPS(R2) 

3041081009CA 

Yes 

Not listed 

Not listed 

Yes 

 
 
 

Safety regulations: Please read these instructions completely before using the equipment. Keep these 
instructions on to hand. The device may only be installed by trained specialist staff. 

 

Installation: 

1) The device is designed for devices and systems 
that meet the standard requirements for hazardous 
voltages, power, and fire prevention. 
2.) Installation and service only by trained persons. 
The AC power must be switched off. The work is to be 
labelled; accidental reconnection of the system must 
be prevented. 
3.) Opening the device, its modification, loosening 
bolts, or operation outside the specified herein 
specification or in an unsuitable environment, has the 
immediate loss of warranty to follow. We disclaim any 
responsibility for any resulting damage to persons or 
things. 
4.) Note: The device must not be operated without an 
upstream circuit breaker (CB). The CB must not be 
larger than 16A. 

 

Warning

Non-compliance these warnings can result in fire 
and serious injury or death.

 

1. Before connecting the device to the AC 
network, make wires free of voltage and assure 
accidentally switch on. 
2. Allow neat and professional cabling. 
3. Never open nor try to repair the unit. Inside 
are dangerous voltages that can cause electrical 
shock hazard. 
4. Avoid metal pieces or other conductive 
material to fall into the item

 

5. Do not operate the device in damp or wet 
conditions 
6. Do not operate the unit under EX-conditions 
7. Do not operate the unit with then capacitive 
load 

 
 
 
 
 
 

Summary of Contents for ESB101

Page 1: ...35mm DIN Rail Wall mount universal case Spring type terminals 6mm 10AWG Integrated bypass relay Capacitive load 1 500uF up to 10 000uF Integrated thermal protection IP20 UL94V 0 case DIN43880 for DIN VDE0603 cutout box EN62368 1 EN55032 class B The ESB is a budget priced inrush peak current limiter for high loads in LED applications complex automation systems and in the machine building The ESB101...

Page 2: ...C dump drop out voltage AC Current 16A continuous load current Power Supply No external power supply required item is self powering Power consumption 2 2W 115Vac 1 1W 230Vac Limiting Cycles Between each limiting action shall be a break of 20 sec to let the device cool down until the next limiting starts Internal Protection Thermal fuse protects from overheat fire Cooling Natural convection Operati...

Page 3: ...01 Fig 5 As soon as the AC recovers the inrush will be limited again Fig 2 3 The ESB101 models provide an internal temperature control In case of a failure the device shuts down to safely prevent from overheating or fire Fig 1 Field Applications The ESB101 limiter allows connecting much more capacitive loads e g LED power supply LED driver to a pre installed circuit breaker CB Fig 1 The ESB avoids...

Page 4: ...of an upstream connected circuit breaker the R M S is the key value of the inrush current not the peak current The thermal trigger point will not be met even while using an extreme fast CB All dominant is the magnetic trigger current By using the empirical formula I peak x 0 707 factor I r m s the tripping current can be defined exact Bear in mind that all the higher the inrush current is all the ...

Page 5: ...e ESB101 to any old surface Connections Clamping Yoke Connector Specifications Input Output connections Tightening torque min max 0 5 0 6Nm blade 1 0x5 5 DIN5264 Touch safe protection acc to DIN VDE 0470 IP20 plugged IP10 unplugged Clamping range min max 0 18 6mm AWG26 AWG10 Solid H05 07 V U min max 0 18 6mm Stranded H05 07 V U min max 0 22 4 mm w plastic collar ferrule DIN 46228 pt 4 min max 0 5 ...

Page 6: ...s ESB101 23 R2 3041081003CA Yes Yes Yes Yes ESB101 33 R2 3041081004CA Yes Yes Yes Yes ESB101 LED 230VAC R2 3041081005CA Yes Yes Yes Yes ESB101 LED 115VAC R2 3041081006CA Yes Yes Yes Yes ESB101 23S 115VAC R2 3041081007CA Yes Yes Yes Yes ESB101 05UPS R2 3041081009CA Yes Not listed Not listed Yes Safety regulations Please read these instructions completely before using the equipment Keep these instru...

Page 7: ...de risquant d entraîner des blessures Español Instrucciones de instalación Lea primero Conserve este manual como referencia para futuras consultas La fuente de alimentación solo puede ser instalada y puesta en funcionamiento por personal cualificado Por favor lea detenidamente este manual antes de conectar la fuente de alimentación Si se produce un fallo o mal funcionamiento durante la operación d...

Reviews: