ESB101(R2) MANUAL
Camtec Power Supplies GmbH - Gewerbestrasse 30 - DE-76327 Pfinztal / Germany
P.6/7 (06/2016.02.4)
Phone +49 (721) 46596-0 - Fax +49 (721) 46596-77 –
www.camtec-gmbh.com
-
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
Mounting Instructions
Follow the above mounting restrictions to allow maximum lifetime of the product and to prevent from tripping the
internal temperature protection fuse. The ESB101 is an active device. The distance between an ESB101 and the next
active or temperature sensitive device shall be 17,5mm or larger. The power consumption of the device is constant at
continuous operation (2,2W @ 115Vac / 1,1W @ 230Vac). Make sure that the ventilation holes below and above the
unit are not blocked to allow free air convection.
Operation
Temperature
Ambient
Temperature
ESB101, 115Vac, AC 16A current
ANSI / UL 508
-40°C … +55°C
CAN / CSA C22.2
-40°C … +55°C
IEC EN62368-1 / IEC EN60950-1
-40°C … +60°C
ESB101, 230Vac, AC 10A current
ANSI / UL 508
-40°C … +55°C
CAN / CSA C22.2
-40°C … +55°C
IEC EN62368-1 / IEC EN60950-1
-40°C … +60°C
ESB101, 230Vac, AC 16A current
ANSI / UL 508
-40°C … +50°C
CAN / CSA C22.2
-40°C … +50°C
IEC EN62368-1 / IEC EN60950-1
-40°C … +55°C
Table of the standards
Product Code
Camtec Article No.
IEC / EN 62368-1
IEC / EN 60950-1
ANSI / UL508 listed
UL-File E485106
CAN / CSA 22.2 listed
UL-File E485106
GHOST EAC #0658490
RU C-DE.MO10.B.02970
ESB101.16(R2)
3041081001CA
Yes
Yes
Yes
Yes
ESB101.23S(R2)
3041081002CA
Yes
Yes
Yes
Yes
ESB101.23(R2)
3041081003CA
Yes
Yes
Yes
Yes
ESB101.33(R2)
3041081004CA
Yes
Yes
Yes
Yes
ESB101.LED.230VAC(R2)
3041081005CA
Yes
Yes
Yes
Yes
ESB101.LED.115VAC(R2)
3041081006CA
Yes
Yes
Yes
Yes
ESB101.23S.115VAC(R2)
3041081007CA
Yes
Yes
Yes
Yes
ESB101.05UPS(R2)
3041081009CA
Yes
Not listed
Not listed
Yes
Safety regulations: Please read these instructions completely before using the equipment. Keep these
instructions on to hand. The device may only be installed by trained specialist staff.
Installation:
1) The device is designed for devices and systems
that meet the standard requirements for hazardous
voltages, power, and fire prevention.
2.) Installation and service only by trained persons.
The AC power must be switched off. The work is to be
labelled; accidental reconnection of the system must
be prevented.
3.) Opening the device, its modification, loosening
bolts, or operation outside the specified herein
specification or in an unsuitable environment, has the
immediate loss of warranty to follow. We disclaim any
responsibility for any resulting damage to persons or
things.
4.) Note: The device must not be operated without an
upstream circuit breaker (CB). The CB must not be
larger than 16A.
Warning
:
Non-compliance these warnings can result in fire
and serious injury or death.
1. Before connecting the device to the AC
network, make wires free of voltage and assure
accidentally switch on.
2. Allow neat and professional cabling.
3. Never open nor try to repair the unit. Inside
are dangerous voltages that can cause electrical
shock hazard.
4. Avoid metal pieces or other conductive
material to fall into the item
5. Do not operate the device in damp or wet
conditions
6. Do not operate the unit under EX-conditions
7. Do not operate the unit with then capacitive
load