Model 109SS Temperature Probe 

3.  Installation and Wiring 

3.1  Burial 

The 109SS is suitable for shallow burial only.  It should be placed horizontally 
at the desired depth to avoid thermal conduction from the surface to the 
thermistor.  Placement of the cable inside a rugged conduit may be advisable 
for long cable runs, especially in locations subject to digging, mowing, traffic, 
use of power tools, or lightning strikes. 

3.2  Submersion 

The 109SS can be submerged to 150 ft (63 psi).  Please note that the 109SS is 
not weighted.  Therefore, the installer should either add a weighting system or 
secure the probe to a fixed or submerged object such as a piling. 

4.  Wiring 

Connections to Campbell Scientific dataloggers are given in Table 4-1.  
Temperature is measured with one single-ended input channel and a Voltage 
Excitation channel.  Multiple probes can be connected to the same excitation 
channel (the number of probes per excitation channel is physically limited by 
the number of lead wires that can be inserted into a single voltage excitation 
terminal, approximately six). 

TABLE 4-1.  Connections to Campbell Scientific Dataloggers 

 
 
 
 
Color 

 
 
 
 
Description 

CR200(X) 
CR800 
CR850 
CR3000 
CR1000 

 
 
CR510 
CR500 
CR10(X) 

 
CR5000 
21X 
CR7 
CR23X 

Black Excitation 

Switched 
Voltage 
Excitation 

Switched 
Voltage 
Excitation 

Switched 
Voltage 
Excitation 

Red Temperature 

Signal 

Single-Ended 
Input 

Single-Ended 
Input 

Single-Ended 
Input 

Purple Signal 

Ground 

 

 

AG 

 

 

Clear Shield 

 

 

 

 

 

5.  Programming 

This section is for users who write their own datalogger 
programs.  A datalogger program to measure this sensor can be 
generated using Campbell Scientific’s Short Cut Program 
Builder software.  You do not need to read this section to use 
Short Cut. 

NOTE 

Summary of Contents for TEMPERATURE PROBE 109SS

Page 1: ...Model 109SS Temperature Probe Revision 12 10 C o p y r i g h t 1 9 8 3 2 0 1 0 C a m p b e l l S c i e n t i f i c I n c...

Page 2: ...International customers residing in countries served by Campbell Scientific Inc directly Affiliate companies handle repairs for customers within their territories Please visit www campbellsci com to...

Page 3: ...am for CR200 X Series Datalogger 6 5 1 1 2 Example 2 Sample Program for CR1000 Datalogger 6 5 1 1 3 Sample Program for CR5000 7 5 2 Edlog 7 5 2 1 Example Edlog Program 7 5 3 Electrical Noisy Environme...

Page 4: ......

Page 5: ...fast time response This probe measures temperature from 40 to 70 C The thermistor can survive temperatures up to 100 C but the overmolded joint and cable should not be exposed to temperatures greater...

Page 6: ...nformation Thermistor BetaTherm Micro BetaCHIP Probe 10K3MCD1 0 018 diameter 10Kohms at 25 C Probe stainless steel sheath 0 063 inch 0 16 cm diameter 2 3 inch 5 84 cm length overmolded joint 0 40 inch...

Page 7: ...6 C over the range of 40 to 70 C and 0 49 C over the range of 20 C to 70 C The major error component is the interchangeability specification tolerance of the thermistor The bridge resistor has a 0 1 t...

Page 8: ...d with one single ended input channel and a Voltage Excitation channel Multiple probes can be connected to the same excitation channel the number of probes per excitation channel is physically limited...

Page 9: ...rm109 is used to measure temperature Therm109 provides excitation makes a single ended voltage measurement and calculates temperature The Therm109 instruction has the following form Therm109 Dest Repe...

Page 10: ...0 EndTable BeginProg Scan 1 sec Measure the temperature Therm109 Air_Temp 1 1 Ex1 1 0 0 Call the data table CallTable AvgTemp NextScan EndProg 5 1 1 2 Example 2 Sample Program for CR1000 Datalogger C...

Page 11: ...the resistance lnRt Log Rtherm Apply the Steinhart and Hart equation and convert to degrees C in one step Air_Temp 1 1 129241e 3 2 341077e 4 lnRt 8 775468e 8 lnRt 3 273 15 Call the data table CallTab...

Page 12: ...c V_Vx 7 1 0 Mult 8 0 0 Offset 2 Z 1 X P42 1 1 X Loc V_Vx 2 2 Z Loc Vx_V 3 Z X F P34 1 2 X Loc Vx_V 2 1 F 3 3 Z Loc Vx_V_1 4 Z X F P37 1 3 X Loc Vx_V_1 2 24900 F 3 4 Z Loc Rtherm 5 Z LN X P40 1 4 X Lo...

Page 13: ...integration options are not available for the CR200 X 5 4 Long Lead Lengths Additional settling time may be required for lead lengths longer than 300 feet where settling time is the delay before the m...

Page 14: ...sary for general operation of the 109SS Probe with CSI s dataloggers The Therm109 Instruction outputs a 2500 mV excitation and measures the voltage across the 24 9 K resistor Figure 6 1 The thermistor...

Page 15: ...on form and comply with the requirements specified in it Refer to the Warranty and Assistance page for more information 8 Troubleshooting Symptom Temperature is NAN INF 9999 273 Verify the red wire is...

Page 16: ...stable Temperature Try using the 60 Hz or 50 Hz integration options and or increasing the settling time as described in Sections 8 and 9 Make sure the clear shield wire is connected to datalogger grou...

Page 17: ......

Page 18: ...p CSC 11564 149th Street NW Edmonton Alberta T5M 1W7 CANADA www campbellsci ca dataloggers campbellsci ca Campbell Scientific Centro Caribe S A CSCC 300 N Cementerio Edificio Breller Santo Domingo Her...

Reviews: