TB4, TB4MM, CS700, and CS700H Tipping Bucket Rain Gages
8
FIGURE 7-1. CS700H with Cables
The sensor cable connects to the data logger (TABLE
). The power cable
connects to the power supply (TABLE
shows the terminals
for connecting the power cable to the Phoenix Contact Power Supply.
TABLE 7-2. CS700H Sensor Cable Wire Color, Wire Function,
and Data Logger Connection
Wire
Color
Wire
Function
Data Logger
Connections Using a
Pulse Terminal
Data Logger
Connections Using a
Control Terminal
Green
SDI-12
Odd-numbered
C
or
U
1
configured for SDI-12
Odd-numbered
C
or
U
1
configured for SDI-12
Red
SDI-12 Power
12V
12V
Blue
SDI-12 Power
Ground
G
G
Black
Rain Signal
P
or
U
1
(Pulse Terminal)
C
2
(Control Terminal)
White
Rain Signal
Reference
⏚
(Analog Ground
)
5 V
Clear
Shield
⏚
(Analog Ground
)
⏚
(Analog Ground
)
1
U
and
C
terminals are automatically configured by the measurement instruction.
2
When using a CR6 or CR1000X, a conflict occurs if the pulse measurement uses an
even C terminal that immediately follows the SDI-12 terminal. For example, if C1 is
used for the SDI-12 terminal, do not use C2 for the pulse terminal.
TABLE 7-3. CS700H Power Cable Wire Color,
Wire Function, and Power Supply Connection
Wire Color
Description
Power Supply
Red
+24 VDC
+
Black
Ground
–
Sensor Cable
Power Cable