![Campbell DustVue Product Manual Download Page 12](http://html1.mh-extra.com/html/campbell/dustvue/dustvue_product-manual_3848902012.webp)
6.2 Modbus TCP communications
Format:
TCP IP
Supported functions:
03
Modbus address:
11
Data type:
32-bit float, CDAB
6.3 System
Clock accuracy:
±1 minute per month
Clock resolution:
1 ms
Program execution:
1 min
6.4 Power requirements
Charger input (CHG):
16 to 32 VDC, current limited at 0.9 A. Power converter or
solar panel input.
External batteries (BAT):
12 VDC, lead-acid 7 Ah battery, typical
Internal lithium battery:
3 V coin cell CR2016 (Energizer) for battery-backed clock. 6
year life with no external power source.
Typical power requirements:
Sleep:
1.5 mA
Active 1 Hz scan with
analog measurement:
5 mA
USB power (USB):
For programming and limited functionality
6.5 Compliance
IEC 61724-1 (2021) compliant. View compliance documents at
.
DustVue
10