34
5.2 Resetting
– Energy meter reset
– Maximum value pointer reset
5.3 Programming the SINEAX DME 406
There are two ways to confi gure the SINEAX DME 406:
1) via RS 232, with PC software DME 4
2) via PROFIBUS-DP Interface with DBF fi le
Table 2: Programming
DESCRIPTION
Application
A11 … A16
A34
A24 / A44
1. Application
(system)
Single-phase AC
A11
–––
–––
3-wire, 3-phase symmetric load, phase-shift U: L1-L2, I: L1
A12
–––
–––
3-wire, 3-phase symmetric load
A13
–––
–––
4-wire, 3-phase symmetric load
A14
–––
–––
3-wire, 3-phase symmetric load, phase-shift U: L3-L1, I: L1
A15
–––
–––
3-wire, 3-phase symmetric load, phase-shift U: L2-L3, I: L1
A16
–––
–––
3-wire, 3-phase asymmetric load
–––
A34
–––
4-wire, 3-phase asymmetric load
–––
–––
A44
4-wire, 3-phase asymmetric load, open Y
–––
–––
A24
2. Input voltage
Rated value Ur = 57.7 V
U01
–––
–––
Rated value Ur = 63.5 V
U02
–––
–––
Rated value Ur = 100 V
U03
–––
–––
Rated value Ur = 110 V
U04
–––
–––
Rated value Ur = 120 V
U05
–––
–––
Rated value Ur = 230 V
U06
–––
–––
Rated value Ur
[V]
U91
–––
–––
Rated value Ur = 100 V
U21
U21
U21
Rated value Ur = 110 V
U22
U22
U22
Rated value Ur = 115 V
U23
U23
U23
Rated value Ur = 120 V
U24
U24
U24
Rated value Ur = 400 V
U25
U25
U25
Rated value Ur = 500 V
U26
U26
U26
Rated value Ur
[V]
U93
U93
U93
Lines U01 to U06:
Only for single-phase AC current or 4-wire, 3-phase symmetric load
Line U91: Ur [V] 57 to 400
Line U93: Ur [V] > 100 to 693
3. Input current
Rated value Ir = 1 A
V1
V1
V1
Rated value Ir = 2 A
V2
V2
V2
Rated value Ir = 5 A
V3
V3
V3
Rated value Ir > 1 to 6
[A]
V9
V9
V9
4. Primary rating
(primary transformer)
Without specifi cation of primary rating
W0
W0
W0
CT =
A / Ir
A
VT =
kV / Ur
V
W9
W9
W9
Line W9: Specify transformer ratio prim. 1000 A; 33 kV
Table 2 continued on next page