Modification
Date Vis.:
Type:
EMMOD201
Nr.:
20 / 26
gez.:
26.11.02 RR
27.02.09 RR
Description:
Interface definition EMMOD201 V2.0
Zeichnr.:
W2414e
BYTE Diga_Konfig[2]
(Reg. 538 low, Reg. 539 high)
- Digital output: Configuration for alarm monitoring
Value
Measurand
A210/A220
A230
single
line,
3/4L bal.
3-wire
asymmetr.
4-wire
asymmetr.
0
Current
•
•
I
I
I
1
Average current
•
•
I.avg
I.avg
I.avg
2
Phase-to-phase voltage
•
•
-
U.LL
U.LL
3
Phase-neutral voltage
•
•
U
-
U.LN
4
Active power
•
•
P
P
P
5
Reactive power
•
•
Q
Q
Q
6
Apparent power
•
•
S
S
S
7
Power factor
•
•
PF
PF
PF
8
P interval
(inc.-outg.)
•
P.int
P.int
P.int
9
Q interval
(ind.+capac.)
1)
Q.int
Q.int
Q.int
10
S interval
•
•
S.int
S.int
S.int
11
Neutral current
•
•
-
-
in
12
Frequency
•
•
F
F
F
13
THD voltage
-
2)
THD.U
THD.LL
THD.LN
14
THD current
-
2)
THD.I
THD.I
THD.I
15
zero displacement voltage
-
2)
-
-
U.NE
16
Unbalanced factor
-
2)
-
-
unb.U
17
P Interval Incoming
-
2)
P.int
P.int
P.int
18
Q Interval cap./Outgoing
-
1)2)
Q.int
Q.int
Q.int
19
P Interval Incoming
Trend
-
2)
P.int
P.int
P.int
20
Q Interval ind./Inc.
Trend
-
1)2)
Q.int
Q.int
Q.int
21
S Interval
Trend
-
2)
S.int
S.int
S.int
22
P Interval Outgoing
Trend
-
2)
P.int
P.int
P.int
23
Q Interval cap./Outg.
Trend
-
1)2)
Q.int
Q.int
Q.int
24-63 Reserved
Line measurands: Will be OR-combined for ON limit, resp. AND-combined for OFF limit.
Example for I
(ON limit
>
OFF limit): Limit output to "ON", if one of the 3 phase currents exceeds the
ON limit and "OFF" if all phase currents are below the OFF limit.
Example for I
(ON limit < OFF limit): Limit output to "ON", if one of the 3 phase currents falls below
the ON limit and "OFF" if all phase currents exceed the OFF limit.
1) The active reactive power intervals for the A230 arise from the configuration in 'Disp_Mode'.
2) For A230 only