48/89 Device handbook A
PLUS
with / without LED display
,
157
679-19, 04/2016
►
Ethernet (Modbus/TCP-interface)
Menu
Range of values
Description
IP
z.B. 192.168.057.011
IP address: Must be unique for each device !
SUb.n
z.B. 255.255.255.000
Subnet mask
GAtE
z.B. 192.168.057.001
Gateway address
PoRT
1...65535
The TCP port for the Modbus/TCP communication,
usually this is port 502.
►
Profibus DP
Menu
Range of values
Description
Addr
0…125
Device address; must be unique within the Profibus network.
bAUd
9.6 kBd … 12 MBd
Transmission speed on the Profibus interface. The present value set is
displayed (auto detection).
c.prm
On
/
OFF
Check_User_Prm
: The parameters of the control system will be used
(On) or declined (OFF). Default: On.
run
On
/
OFF
Go_Online
: Device is able to connect to the control system (On) or is
separated from the Profibus system (OFF). Default: On.
set.a
On
/
OFF
Set_Slave_Addr_Supp
: Setting of the device address via Profibus master
is allowed (On) or disabled (OFF). Default: On.
Res.a
On
/
OFF
If On the device address is reset to the factory setting (126). In this case
the device is no longer able to communicate with the control system.