14/89 Device handbook A
PLUS
with / without LED display
,
157
679-19, 04/2016
4. Mechanical mounting
► The standard version of the A
PLUS
is designed for panel mounting as shown below
► The version without display with top-hat rail adapter may be clipped onto a top-hat rail according to
EN50022
Please ensure that the operating temperature limits are not exceeded when
determining the place of mounting (place of measurement):
-10 ... 55°C
4.1 Panel cutout
Dimensional drawing A
PLUS
:
See section 10
4.2 Mounting of the device
The A
PLUS
is suitable for panel widths up to 10mm.
a) Slide the device into the cutout from
the outside
b) From the side slide in the mounting
clamps into the intended openings and
pull them back about 2 mm
c) Tighten the fixation screws until the
device is tightly fixed with the panel
4.3 Demounting of the device
The demounting of the device may be performed only if all connected wires are out of service. Remove
all plug-in terminals and all connections of the current and voltage inputs. Pay attention to the fact, that
current transformers must be shortened before removing the current connections to the device. Then
demount the device in the opposite order of mounting (4.2).