6
Section 1
Model 580A Differential Pressure Switch
Specifications
General
Actuating Unit (DPU) ...................... Model 224 DPU
Dial Size ......................................... 6 inches (150 mm)
Service Conditions (Normal)........... 40°F (4.4°C) to +180°F (+82.2°C) @ <90% R.H.
Switch Repeatability ....................... ±1% of calibrated span
Switch Set-point Range .................. 10 to 90% of calibrated span
Switch Deadband ........................... ±10% of calibrated span (maximum)
Switch Type .................................... Mechanical, Snap-Acting; both switches are SPDT
Activation ........................................ Increasing or decreasing scale
Switch Contact Rating:
5.0 Amps @ 125 VAC
5.0 Amps @ 250 VAC
3.0 Amps @ 30 VDC (resistive)
1.0 Amp @ 30 VDC (inductive w/arc suppression)
0.4 Amp @ 125 VDC (resistive)
0.2 Amp @ 125 VDC (inductive w/arc suppression)
Input Range .................................... 0-30" WC to 0-650 psid
Indicator Accuracy .......................... ±2.0% of calibrated span (for ranges to 400 psid)
1,2
Indicator Repeatability .................... ±0.5% of calibrated span
Safe Working Pressure ................... 500, 1000, 1500, 3000, or 6000 psig
Maximum Overrange ...................... To safe working pressure
Process Connections...................... 1/4" x 1/4", 1/4" x 1/2", 1/2" x 1/4" and 1/2" x 1/2"
(top x bottom)
Electrical Connections .................... Female, 3/4" NPT, 20 ft., color-coded Tefzel®
insulated 18 AWG wire (40 ft. leads available by
special order)
Torque Tube Rotation ..................... 8° (nominal)
1
± 2.5% of calibrated span for ranges between 400 and 600 psid; ±6% for ranges over
600 psid.
2
Additional 2% is applicable near the switch setpoints (±10% span).
Nuclear Qualifications
The following nuclear qualification applications are based on Cameron Engi
-
neering Report 9A-CR3-580A-29 and 9A-CR3-580A31.
Design Basis Event (DBE) Performance Error
1
(% of calibrated span):
Radiation (1 x 10
7
Rads) ................ ±10%
Seismic (12.5 Gs):
During Event ................................... ±10%
Following Event .............................. ±5%
Harsh Environment (≤ 200°F):
During Event ................................... ±10%
Following Event .............................. ±10%
1