For switch troubleshooting tips, see Table 3.2 below. For information related
to the Model 224 DPU, see
Table A.3, page A-15
.
Table 3.2—Troubleshooting
Problem
Possible
Source
Probable Cause
Corrective
Action
Low or No
Indication
Indicator,
Alarm Switch
Mechanism
Loose linkage or movement
Tighten or replace
Out of calibration
Calibrate
Pointer loose
Tighten pointer
Dirty or corroded mechanism
Clean or replace
Wiring interfering with movement
Re-route wiring
Dirty mechanism
Clean mechanism
High
Indication
Indicator,
AlarmSwitch
Mechanism
Loose linkage or movement
Tighten or replace
Out of calibration
Calibrate
Erratic
Indication
Indicator,
Alarm Switch
Mechanism
Linkage dragging or dirty
Adjust or clean
Pointer dragging on scale plate
Adjust pointer
position
Inaccurate
or No
Electrical
Alarm
Power
Supply
Blown fuse
Replace fuse
Broken or loose wire
Repair
Alarm Switch Switch not properly adjusted
Adjust switch
Dirty or burned contacts
Replace switch