Pairing Secure Lock Relay with Call Panel 

10 

6

 

Pairing Secure Lock Relay with Call Panel 

6.1

 

Confirm Door No. of Call Panel 

i.  Connect a laptop or PC to the same network as the Call Panel. 

ii.  Use a web browser and enter the IP address of the Call Panel in to the address bar. 

iii.  Login to the call panel using the username 

admin

 and the device admin password. 

iv.  Navigate to Local Settings > Basic. 

v.  Check the 

Door No.

 - each Call Panel on a block should have a unique number. 

 

FIGURE 6-1 

6.2

 

Secure Lock Relay RS485 Address 

  The Secure Lock Relay has connections for up to 4 doors and must have the RS485 

address corresponding to the last 2 digits within the Door No. of the associated Call Panels. 

  The RS485 address must correspond to the address of the 1

st

 Call Panel, then the 

subsequent Call Panels Door No. are incremented.  E.g. 

o

  4 Doors numbered 80

01

-80

04

 = RS485 address 

1

o

  4 Doors numbered 81

05

-81

09

 = RS485 address 

5

  SW1 Switches 1-4 set the binary address (0-15). 

 

 

Switch 

Always 

ON 

Always 

ON 

Binary Value 

Address 0 

Address 1 

Address 3 

Address 7 

Address 15 

 

FIGURE 6-2 - BINARY ADDRESS TABLE 

 

ON = 1 

OFF = 0 

Summary of Contents for ENTROTEC PRO-DC4

Page 1: ...PRO DC4 installation SETUP guide Issue 001 December 2022 came com entrotec...

Page 2: ...ng Regulations 18th Edition Regulation 444 MEASURES AGAINST ELECTROMAGNETIC DISTURBANCES imposes requirements for segregation of circuits IET Wiring Regulations 18th Edition Regulation 528 PROXIMITY T...

Page 3: ...Exit Switch Connections 7 4 2 Fail Open Lock Connection 7 4 3 Fail Closed Lock Connection 7 4 4 Emergency Door Release 7 4 5 Lock Suppression 8 5 Call Panel connections 8 5 1 Connections from SLR 8 5...

Page 4: ...he specification below shows the minimum cable requirements allow for extra cabling if redundancy is required Connection Cable A Door controller to each call panel 2x Cat5e or Cat6 B Lock Relay to loc...

Page 5: ...Overview 5 2 Overview FIGURE 2 1 Item Connection Detail Power Supply Unit PSU Section 3 Page 6 Secure Lock Relay Section 4 Page 7 Network Switch Section 5 2 Page 9 A B C B A C...

Page 6: ...Point Pre Wired 12V to Internal Devices Backup Battery Connections for Sealed Lead Acid Battery Output Voltage Adjustment SYSTEM VOLTAGE 13 8VDC Always test the output voltage Only adjust if required...

Page 7: ...re switches with fail open locks see section 4 2 4 2 Fail Open Lock Connection Connection for fail open locks power to hold e g magnetic locks FIGURE 4 2 4 3 Fail Closed Lock Connection Connection for...

Page 8: ...ssible This prevents back EMF and spikes from damaging equipment and causing erratic operation WARNING Failure to fit adequate suppression may invalidate any warranty SUITABLE SUPPRESSION CAME Entrote...

Page 9: ...ble Type Detail RS485 from Call Panel Splitter 1x Cat5e or Cat6 1 Pair UTP RS485A RS485B 12VDC from Call Panel Splitter 1 Pair UTP 12v White 2 Pair UTP 0v Black Ethernet to Network Switch 1x Cat5e or...

Page 10: ...RE 6 1 6 2 Secure Lock Relay RS485 Address The Secure Lock Relay has connections for up to 4 doors and must have the RS485 address corresponding to the last 2 digits within the Door No of the associat...

Page 11: ...Device List 11 7 Device List IP Address Block ID SIP ID Type Description 192 168 1 111 1 8001 Call Panel Ashwood Court Front Door...

Page 12: ...rotec PRODCGUIDE0322 2022 EN YOU MAY NOT EVEN PARTIALLY REPRODUCE THIS DOCUMENT THE DATA AND INFORMATION SHOWN IN THIS CATALOGUE ARE SUBJECT TO CHANGE WITHOUT OBLIGATION TO GIVE PRIORNOTICE BY CAME S...

Reviews: