GENERAL INSTALLATION INSTRUCTIONS
⚠
Installation must be carried out by qualified and experienced personnel in compliance with applicable regulations.
Preliminary checks
⚠
Before starting installation:
•
Provide a suitable single-pole disconnection device, with a maximum of 3 mm between the contacts, to disconnect the
power supply;
•
Prepare suitable piping and ducts for routing the electrical cables, ensuring protection against mechanical damage;
•
Make sure that any connections within the container (made to ensure the continuity of the protection circuit) are
fitted with additional insulation compared to the other internal conductor parts;
•
Check that the door is well-balanced. If it is halted at any intermediate point, it must maintain the position;
•
If there is a pedestrian opening in the door, a safety switch must be added, connected to the stop input, in order to
prevent the operator from being operated when the pedestrian door is open.
•
Check that the movement of the door is uniform along the whole stroke, that there is no friction or gaps between the
sliding rails and bearings
❶
and that the pulleys
❷
are in good condition;
•
Check that the structure of the door is robust and that the hinges
❸
are efficient.
Tools and materials
Make sure you have all the tools and materials you will need for the installation at hand to work in total safety and compliance
with current standards and regulations. The figure shows some examples of installer’s tools.
Types of cables and minimum thicknesses
Connection
Cable type
Cable length
1 < 10 m
Cable length
10 < 20 m
Cable length
20 < 30 m
Board power supply 230 VAC
FROR CEI
20-22
IEC EN
50267-2-1
3G x 1.5 mm
2
3G x 2.5 mm
2
3G x 4 mm
2
24 VDC motor power supply
2 x 1,5 mm
2
2 x 1.5 mm
2
2 x 2.5 mm
2
Flashing light
2 x 0.5 mm
2
2 x 1 mm
2
2 x 1.5 mm
2
Photocell transmitters
2 x 0.5 mm
2
2 x 0.5 mm
2
2 x 0.5 mm
2
Photocell receivers
4 x 0.5 mm
2
4 x 0.5 mm
2
4 x 0.5 mm
2
Control and safety devices
2 x 0.5 mm
2
2 x 0.5 mm
2
2 x 0.5 mm
2
Antenna
RG58
max. 10 m
Encoder
TWISTED
max. 30 m
N.B. If the cables differ in length compared to what is shown in the table, the cable cross-section is determined according to the
actual current draw of the devices connected and according to the provisions of the IEC EN 60204-1 standard.
For connections that require several, sequential loads, the sizes given on the table must be re-evaluated based on actual
power draw and distances. When connecting products that are not specified in this manual, please refer to the documentation
provided with said products.