CX-DA400 Door Prop Alarm Installation Instructions
Page 5 of 6
ADDITIONAL FEATURES
SEE COMPONENT LOCATION DIAGRAM ON PAGE 2
7
BYPASS
TS1
(9&10) input, to
N/O contact to
remotely Bypass or
Reset the unit.
REMOTE LED
to TS1 (5&6).
ADDITIONAL OUTPUT INFORMATION
•
Each of the Output functions offers the availability
of monitoring a Normally Open or a Normally
Closed Dry contact.
•
Each contact’s state will change to follow the status
of the monitored function.
•
To combine multiple outputs, connect N/O contacts
in parallel, or N/C contacts in series.
See diagrams at right. The use of any/all Outputs
is optional.
•
If power is removed from the CX-DA400, each contact in it’s normal
state (powered), will change state. Example: Door Status will appear as
if the door
has been opened; Alarm and Bypass contacts will appear as if an alarm
or bypass condition exists.
HORN VOLUME -
Jumper 10 is used
to set the volume of
the sounder.
ON = 103db
OFF = 96db
TROUBLE SHOOTING TIPS
• Horn won’t Reset
- Verify Tamper Switch is closed; Verify
Door Supervision Jumper is correct for application; Check
Door Contact Resistors are installed as per Step 1 if Door
Supervision is enabled.
• LED always Green
- Normal condition when Jumper 4 is OFF;
Verify Shunt Contact & Voltage Sense jumpers are correct for
your application; Verify Key Switch is Vertical and Bypass Input
is open.
• Alarm when Door Opens
- Verify that SO&S1 Jumpers and
Silent Time are set greater than 0 sec.; Verify Intrusion Jumper
is set correctly for application.
• Clicking Output Relays
- Verify Jumper 6 (Reserved) is OFF.
ELECTRICAL SPECIFICATIONS
Power
12-24 VAC/DC 250mA
Voltage Sense
12-24 VAC/DC
15mA
Shunt Input
Jumper Select
Bypass Input
✔
Door Input
✔
Output Relays
Dry Contact
1 Amp@
30 VDC
✔ ✔
VOLTS
AMPS N/O N/C
N/A
Dry Contact
Dry Contact
Dry Contact
MECHANICAL SPECIFICATIONS
• The CX-DA400 mounts flush in a 2.5” (63 mm) deep, 2-Gang
electrical box.