CX-DA400 Door Prop Alarm Installation Instructions

Page 4 of 6

SHUNT RECYCLE EXPLAINED

 - 

• 

When Shunt Recycle is Enabled (ON), a Shunt Contact or Voltage Sense Input 

during the Alarm Delay warning period (beeping) will reset the Silent Time 

Timer.  Shunt Recycle gives the User the ability to Hold the door indefinitely by 

repeating a valid input during each Alarm Delay warning.

• 

When disabled, only a Key or Bypass input will reset the DMA.

SHUNT INPUT 

EXPLAINED - 

This 

input from a PIR 

or Access Control 

system provides 

user validation.

•  SHUNT RECYCLE 

(see description below)   

A) Jumper 5 is ON

B) Jumper 5 is 

OFF

TIMER SETTINGS 

SEE TABLE ON REVERSE

     

4

•  The 

SHUNT DELAY TIMER

 begins after a Valid User input (prior to 

door being opened) and 

if door is not opened

  the DMA will reset 

when timer expires. Cancels upon door opening.

A) Shunt Delay works only with Intrusion Detection enabled.    

B) See table on Back Plate for Jumper 7&8 setting detail.

•  SILENT TIME SELECT 

begins 

when the door is opened

  

by a valid user. (see 

Timer Setting Table

 on reverse)

A) Timer has 

two ranges

 selected with 

Jumper 9;

• 

Normal -

 0 seconds to 2.5 minutes (Jumper OFF)

• 

Extended -

 3 minutes to 90 minutes (Jumper ON)

B) After selecting appropriate range, turn dial to 

SET #

  

for the Silent Time period desired for your application.

•  ALARM DELAY SELECT 

begins 

on the expiration of the  

Silent Timer.

 Warning Alarm sounds locally to alert user.

A) Turn dial to 

SET #

 on table (see reverse) for the time  

you want the Warning (beeping) alarm to sound (prior to triggering 

the Door Prop Alarm Horn and Relay).

•  AUTO RESET TIME SELECT 

is the minimum time the  

Horn, LED and Relays are on following an alarm condition.

NOTE:

 Alarm will continue for as long as the door is open

A) Turn the dial to SET Timer (0 seconds to 5 minutes,  

or Manual).

 POWER

5

•  POWER - 

Connect 12-24 VAC/DC to TS1 11&12.   

Not polarity sensitive.

OUTPUTS (FORM-C)

6

•  DOOR STATUS RELAY

  

TS2-22,23,24 changes state when the 

Door Input changes. Used to monitor 

changes in Door Contact status.

•  DOOR PROP ALARM RELAY 

 

TS2-19,20,21 changes state when a 

door is held open beyond the Silent and 

Alarm Delay time, combined.

•  FORCED DOOR/TAMPER ALARM 

RELAY 

 

TS2-16,17,18 changes state when a 

door is forced or a tamper condition 

exists (Door Supervision/Tamper 

Switch).

•  BYPASS/KEY SWITCH  

STATUS RELAY 

 

TS2-13,14,15 changes state during Bypass (TS1 9&10) and Key 

Switch Inputs. Used to monitor for changes in Bypass status.