CX-DA400
Door Prop Alarm
Installation Instructions
Page 1 of 6
CONTENTS
COMPONENT LOCATION DIAGRAM
DESCRIPTION
CX-DA400
The CX-DA400 provides complete monitoring of access control points by
offering you prop/door held open and intrusion/door forced open detection.
These alarms are designed to complement card reader and access control
systems and will interface with electronic locks, produce audible warnings
and reduce nuisance alarms by encouraging user compliance with access
control procedures.
OTHER FEATURES
•
Shunt Recycle -
See Step 3. Pg. 4
•
Door Supervision -
See Step 1. Pg. 3
•
Intrusion Detect -
See Step 2. Pg. 3
•
Loud Horn Volume -
See Step 7. Pg. 5
•
Extended Silent Time -
See Step 4. Pg. 4
•
Shunt Delay Timer -
See Step 4 . Pg. 4
INPUTS
The inputs are located on Terminal Strip –1
and include:
• Dry Contact Shunt
- a N/O or N/C Dry
Contact, selected using Shunt Contact
Mode Jumper 3. See Step 3. Pg. 4
• Voltage Sense
- Monitors the power
wires on an electric lock (i.e.: Mag-lock or
Door Strike). Senses change in voltage
as valid user. See Step 3. Pg. 4
• Door Contact
- a Closed Loop (N/C)
Dry Contact which opens when the
monitored door opens. See Step 1. Pg. 3
• Bypass
- Connect to a N/O Dry Contact
from a remote location to bypass the
unit. See Step 7 Pg. 5
• Power
- 12 to 24 VAC/DC @ 250 mA.
The terminals are not polarity sensitive.
See Step 5. Pg. 4
OUTPUTS
• Remote LED
- (located on TS-1)
Output for a remote Bi-color LED,
output follows LED on Face Plate.
• Door Status Relay
- follows the Door
Contact Input, regardless of alarm or
bypass condition.
• Door Prop Alarm Relay
- changes
state during a Door Prop
(Door Held) Alarm condition.
• Intrusion & Tamper Alarm Relay
-
changes state during an Intrusion
or Tamper Alarm condition.
• Bypass/Key Switch Status Relay
-
follows Bypass and Key inputs.
Output contacts change state when power
is lost.
JUMPER
CONFIGURES
1 Door Supervision
(Part of Tamper circuit)
TS1-7&8 Door Input
2 Voltage Sense Mode
(Senses Lock Voltage as Valid User Input)
TS1-3&4 Voltage Sense Input
3 Shunt Contact Mode
(Senses Dry Contact as Valid User Input)
TS1-1&2 Shunt Contact Input
4 Intrusion Detect Enable
(Explained on reverse)
Intrusion or Free Access selection
5 Shunt Recycle Enable
(Explained on reverse)
Shunt Recycle feature selection
6 RESERVED
(Factory Diagnostic)
Factory Use Only Leave Jumper OFF
7 & 8 Shunt Delay Timer
(Set same as Lock Time)
Access Time prior to opening door
9 Extended Time
Select Ext. Silent Time 3-90 Min.
10 Horn Volume
Select 96db or 103db