M-Series Technical Manual
3
Cambridge Engineering, Inc.
TYPICAL SYSTEM OVERVIEW
CONTROL SYSTEMS:
MAXITROL SERIES 14
The Maxitrol Series 14 electronic discharge temperature
control system maintains a constant discharge tempera-
ture. The standard control permits manual adjustment
of discharge temperature (55° to 90°F) from inside the
heater control enclosure. As an option, a Remote Heat
Adjust control with override capability to 130°F can be
provided to allow manual adjustment of discharge tem-
perature (55° to 130°F) from either inside the heater con-
trol enclosure or in the Remote Control Station.
MAXITROL SERIES 14 WITH SPACE
THERMOSTAT
The Maxitrol Series 14 modulation controls function as
described above using the optional Remote Heat Adjust
control in conjunction with an electronic space thermo-
stat switch contact to increase discharge temperature.
The discharge temperature will increase to a preset rise
(0°F to 40°F) above the set point on the Remote Heat
Adjust control face based on the setting of the override
temperature dial, which is visible from the top of the
control.
MAXITROL SERIES 44
The Maxitrol Series 44 modulation controls maintain
a constant space temperature by increasing or decreas-
ing the discharge temperature. The Space Temperature
Selector is set to maintain the space temperature of the
heated space by controlling the heater output between
the MIN and MAX setting on the amplifier. The MIN
dial setting determines the minimum discharge tempera-
ture the heater will deliver (40°F to 80°F). The MAX dial
setting determines the maximum discharge temperature
the heater will deliver (80°F to 140°F).
MAXITROL SERIES 44 / TAMPER PROOF
The Maxitrol Series 44 / Tamper Proof temperature
control system is similar to the Maxitrol Series 44 con-
trols above except the adjustable Space Temperature
Selector control is replaced by two other controls. The
adjustable portion of the temperature selector is typically
mounted in the Remote Control Station to prevent unwanted
tampering of the temperature setting and the non-adjustable
space sensor is mounted in the space being heated.