Cambridge
Air
Solutions
10/31/2022
BACnet
Controller
EVAP
Technical
Manual
Version
4.0.2.0002
MULTISTATE VALUE OBJECTS
Object
Description
Writable
States
Values
MV:29501 Unit
Status
False
4
1 = Heating
2 = Satisfied
3 = Cooling
4 = Temperature Unreliable
MV:29505 FCB Baud Rate
True
6
1 = Auto
2 = 1200
3 = 9600
4 = 19200
5 = 38400
6 = 76800
MV:29506 Operating Baud Rate
False
MV:29507 Supply Fan Status
False
2
1 = Off / 2 = On
MV:29525 Control
Points
True
2
1 = State 0 / 2 = State 1
MV:29534 Supply Fan Fault
False
2
1 = Normal / 2 = Alarm
MV:29535 Sensor 1 Alarms
False
2
1 = Alarm / 2 = Normal
MV:29536 Supply Air Temperature Sensor Failure
False
2
1 = Normal / 2 = Alarm
MV:29537 Outdoor Air Temperature Sensor Failure
False
2
1 = Normal / 2 = Alarm
MV:29538 Zone Temperature Sensor Failure
False
2
1 = Normal / 2 = Alarm
MV:29539 Supply Fan Control Mode
True
3
1 = Hand / 2 = Off / 3 = Auto
MV:29540 Indirect Pump Control Mode
(optional)
True
3
1 = Hand / 2 = Off / 3 = Auto
MV:29541 Drain Valve 1 Control Mode
True
3
1 = Auto / 2 = Close / 3 = Open
MV:29542 Fill Valve 1 Control Mode
True
3
1 = Auto / 2 = Close / 3 = Open
MV:29543 Effective Occupancy
False
2
Occupied / Unoccupied
MV:29544 Occupied Fan Mode
True
3
1 = Auto / 2 = Off / 3 = On
MV:29545 Unoccupied
Fan
Mode
True
3
1 = Auto / 2 = Off / 3 = On
MV:29546 Occupied Cooling Mode
True
3
1 = Auto / 2 = Off / 3 = On
MV:29547 Unoccupied
Cooling Mode
True
3
1 = Auto / 2 = Off / 3 = On
MV:29548 Occupancy
Override
True 5
1 = Occupied
2 = UnOccupied
3 = Bypass
4 = Standby
5 = Not Set
MV:29549 Occupancy
Schedule
MV:29555 Sensor 2 Alarms
False
2
1 = Alarm / 2 = Normal
MV:29557 Cooling Type
True
3
1 = X / 2 = Y / 3 = Z
MV:29541 Drain Valve 2 Control Mode
(optional)
True
3
1 = Auto / 2 = Close / 3 = Open
MV:29542 Fill Valve 2 Control Mode
(optional)
True
3
1 = Auto / 2 = Close / 3 = Open
MV:29562 Direct Pump Control Mode
(optional)
True
3
1 = Hand / 2 = Off / 3 = Auto
MV:29563 Burner Status
False
2
1 = Off / 2 = On
MV:29565 Burner Modulation Mode
True
2
1 = Auto / 2 = Manual
MV:29566 Burner Control Mode
True
3
1 = Hand / 2 = Off / 3 = Auto
MV:29567 Burner Alarm Reset
True
2
1 = Off / 2 = Reset
MV:29568 Heat/Cool Mode
True
2
1 = Heating / 2 = Cooling
MV:29569 Burner Fault
False
2
1 = Normal / 2 = Alarm
MV:29570 DAT Low Temperature Alarm
False
2
1 = Normal / 2 = Lockout
MV:29571 Heater Lockout Alarm
False
2
1 = Normal / 2 = Lockout
MV:29572 System
Mode
False
5
1 = Heat
2 = Cool
3 = Fan Only
4 = Auto
5 = Off