POINTS LISTS
The following lists of points are accessible via the network. Points listed as optional may not be
applicable to all systems.
INPUT OBJECTS
Type
Object
Input#
Description
Writable
Values
Binary MV:29563
BI:1 Burner
Status
(optional)
False
0 = Off / 1 = On
Binary
MV:29507
BI:2
Supply Fan Status
False
0 = Off / 1 = On
Binary
MV:29535
BI:5
Low Water Switch #1
False
0 = Open / 1 = Closed
Binary
MV:29555
BI:6
Low Water Switch #2
(optional)
False
0 = Open / 1 = Closed
Type
Object
Input#
Description
Writable
Units
Range
Analog
AV:29504
UI:14
Discharge air temperature
False
°F
-50 - 250
Analog
AV:29550
UI:15
Water Conductivity #2
(optional)
False
(
μ
S/cm) 0-10,000
Analog
AV:29506
UI:16
Outdoor air temperature
False
°F
-50 - 250
Analog AV:29507 UI:17 Zone
temperature
(optional)
False
°F
-50 - 250
Analog
AV:29508
UI:18
Water Conductivity #1
(optional)
False
(
μ
S/cm) 0-10,000
OUTPUT OBJECTS
Type
Object
Output#
Description
Writable
Values
Binary
MV:29564 BO:4 Burner
command
(optional)
False
0 = Off / 1 = On
Binary
MV:29516 BO:6 Indirect
Pump
command
(optional)
False
0 = Off / 1 = On
Binary
MV:29550 BO:8 Direct
Pump
command
(optional)
False
0 = Off / 1 = On
Binary MV:29520
BO:10
Supply Fan command
False
0 = Off / 1 = On
Binary MV:29521
BO:11
Drain Valve #1 command
False
0 = Open / 1 = Closed
Binary MV:29522
BO:12
Fill Valve #1 command
False
0 = Closed / 1 = Open
Binary MV:29553
BO:13
Drain Valve #2 command
(optional)
False
0 = Open / 1 = Closed
Binary MV:29554
BO:14
Fill Valve #2 command
(optional)
False
0 = Closed / 1 = Open
Type
Object
Output#
Description
Writable
Units
Range
Analog AV:29551 AO:1 Burner
Modulation
(optional)
False
%
0 - 100
Analog AV:29509
AO:2
Supply Fan Output
(optional)
False
%
0 - 100
BINARY VALUE OBJECTS
Object
Description
Writable
Values
BV:29501 System Enable
True
0 = Disable / 1 = Enable
BV:29502 Water System Flush
True
0 = Off / 1 = On
BV:29512 Supply Fan Runtime Reset
True
0 = Off / 1 = Reset
BV:29516 Humidity Lockout Enable
True
0 = Disable / 1 = Enable
BV:29517 Burner Runtime Reset
(optional)
True
0 = Off / 1 = Reset