9.2.3. SA – Technical assistance settings
To enter password is required (see paragraph 10.1.)
N°
Description
Standard Modifications Note
SA01 Restore attempt number
6
SA02 Attempt time
(s)
60
SA03 Pressure PID (Proportional gain)
2,8
SA04 Pressure PID (Integral time constant)
5,5
SA05 Pressure PID (Derivative time constant)
5,0
SA06 Min. run frequency
(Hz)
30
SA07 Max frequency
(Hz)
60
SA08 Set point pressure step up
(bar)
0,3
SA09 Pressure step up time
(s)
3
SA10 Pressure step up ramp
(bar/s)
0,3
SA11 Set point control ramp
(bar/s)
0,4
SA12 Carrier frequency
7010
SA13 Singlephase starting frequency
(Hz)
80
9.2.4. MAn – Fixed speed mode activation
To enter password is required (see paragraph 10.1.)
N°
Description
Standard Modifications Note
MAn1 Fixed speed mode activation
oFF
MAn2 Working frequency
(Hz)
45
[MAn2 ≤ UP03]
a
9.3. Alarms
N°
Displayed alarm
Causes
Er01 Blockage due to no water
The device is in failure due to no water.
The system try to restart automatically.
- One attempt every 10 minutes for 6 times.
- One attempt every hour for 24 times.
- One attempt every 24hours for 30 times.
Er02 Pressure transducer fault
Not connected cable, broken connection, pressure
transducer spoiled.
Er03 Blockage due to low supply voltage
Supply voltage lower than 190V.
- The system automatically restart when the clamp
voltage is higher than 190V.
Er04 Blockage due to high rectified voltage
Supply voltage higher than 250V.
- The system automatically restart when the clamp
voltage is lower than 250V.
Er05 Blockage due to missed setting of the rated
current or rated frequency
Er06 Blockage due to overcurrent in the electro
pump motor
Er07 Blockage due to overcurrent in the
frequency converter
Er08 Blockage due to direct short circuit between
the phases of output terminals
Er09 Blockage due to overheating
Er10 Blockage due to overheating of the power module
Er11 Blockage due to low voltage 24 V
Er12 Stop for float switch intervention
The system will restart after 30 s from the state
variation of the float switch. The control panel
for remote alarm not report this alarm.
Er13 Internal hardware error
Contact the technical assistance
Er14 Cascade mode communication error
Check the RS 485 connection or that both pumps
are enabled.
In case of multiple fault, scroll with the buttons
(plus) or
(minus) to visualize the fault
sequence.
In case of thermal block it is advised to check the causes that have created the problem
before restart the pump operation.
25
All manuals and user guides at all-guides.com
Summary of Contents for EASYMAT 5MM
Page 15: ...15 4 93 412 4 All manuals and user guides at all guides com...
Page 99: ...11 1 2 3 4 2 7 12 5 OFF 12 1 UP UP04 13 1 2 8 83 All manuals and user guides at all guides com...
Page 107: ...91 4 93 414 6 4 93 414 5 4 93 414 4 All manuals and user guides at all guides com...
Page 111: ...95 All manuals and user guides at all guides com...