Before start the system, read the
frequency converter instructions
for the electrical connections.
1. Start
As soon as the EASYMAT is turned on, after an
inital check of the system the display shows
Er06, it will be necessary to set the motor
parameters on the frequency converter with the
following parameters:
-
UP02
nominal current
-
UP03
nominal frequency
-
UP05
set point pressure
2. UP02 nominal current
(see also diagram page 14)
Push the buttons
(menu) and
(enter),
with the button
(plus) move to the parameter
UP02
. Confirm with
(enter) and then with
the buttons
(plus) or
(minus) set the
nominal current of the electric pump that you can
read on the data plate and confirm with
(enter). By pushing the button
(menu) go
out from the parameter.
3. UP03 nominal frequency
(see also diagram page 14)
Push the buttons
(menu) and
(enter),
with the button
(plus) move to the parameter
UP03
. Confirm with
(enter) and then with
the buttons
(plus) or
(minus) set the
nominal frequency of the electric pump that you
can read on the data plate and confirm with
(enter). By pushing the button
(menu) go
out from the parameter.
4. UP05 set point pressure
Push the buttons
(menu) and
(enter).
By pushing the buttons
(plus) or
(minus)
move to the parameter
UP05
and confirm with
(enter) to enter parameter. With the buttons
(plus) or
(minus) change the set point
pressure and confirm with
(enter).
Exit from the program by pushing
(menu)
until you arrive on the basic screen (the set-up
mode icon disappear).
Now the frequency converter is ready to run,
push the button
(play) to change the pump
status from STOP to run.
When the motor starts turning, check
the direction of rotation of the pump.
5. Inversion of the direction of
rotation UP04
(three-phase
motor)
To change the direction of rotation of the motor,
push the button
(menu) and then with the
button
(plus) move up to the programming
parameter UP. Confirm with
(enter) and
with the button
(plus) move up to the
parameter
UP04
, confirm with enter and by
pushing of the button
(plus) change the
value, confirm with
(enter).
To exit the program, push
(menu) until you
reach the basic screen, when you are out from
the set-up mode the icon disappear
.
Now you can start the frequency converter by
pushing the button
(play).
4
Single pump mode
4.93.412.6
All manuals and user guides at all-guides.com
Summary of Contents for EASYMAT 5MM
Page 15: ...15 4 93 412 4 All manuals and user guides at all guides com...
Page 99: ...11 1 2 3 4 2 7 12 5 OFF 12 1 UP UP04 13 1 2 8 83 All manuals and user guides at all guides com...
Page 107: ...91 4 93 414 6 4 93 414 5 4 93 414 4 All manuals and user guides at all guides com...
Page 111: ...95 All manuals and user guides at all guides com...