Technical data
Heat pumps, specialist applications heaters H models
Pro-Pac 30BH
Pro-Pac 45BH
Pro-Pac 70BH
Pro-Pac 90BH
Pro-Pac
140BH
Units
Duty - output to water @ 30°C/55°C
Air on @ 30°C, 90%RH
Electrical input
Air on @ 20°C, 65%RH
Electrical input
Air on @ 10°C, 85%RH
Electrical input
kW
kW
kW
kW
kW
kW
24.5/21.6
5.1/8.0
22.0/19.9
4.4/7.0
18.9/16.8
4.2/6.5
30.6/27.0
6.5/10.2
28.0/24.0
5.8/8.9
23.5/20.1
5.5/8.3
46.2/40.7
9.1/14.8
42.0/37.4
8.1/12.8
35.5/31.7
7.6/11.9
61.2/53.9
13.0/20.5
56.0/49.5
11.5/17.7
47.1/42.0
10.9/16.6
92.3/81.4
18.4/30.0
84.0/74.8
16.2/25.5
71.0/63.3
15.2/23.9
Electrical data
Electrical supply (50 Hz, 3PH)
Minimum supply capacity (3PH)
Recommended supply fuse (3PH)
Max starting curent STD (LRA)
Max starting current soft start (LRA)
V
amps
amps
amps
amps
400
20
30
80
31
400
22
30
102
34
400
35
50
174
40
400
44
60
102
34
40
70
100
174
40
Air data
Nominal air flow
Fan external resistance
Fan external resistance (F)
m³/h
Pa
Pa
5500
0
n/a
10000
0
60
14000
0
60
20000
0
60
28000
0
60
Water Data
Water flow ±10%
Pressure drop (water)
Water connections
Condensate water connections
l/min
m hd
inch
inch
66
2.1
1½ BSPM
1½ BSPM
66
4.2
1½ BSPM
1½ BSPM
130
3.9
1½ BSPM
1½ BSPM
130
4.2
1½ BSPM
1½ BSPM
260
5.3
2 BSPM
1½ BSPM
General data
Gas charge (R134a) BH
Compressor type
Fan type
Sound pressure level @ 3m AIR ON
Sound level @ 3m AIR OFF
Sound level @ 3m SIDE
kg
dB(A)
dB(A)
dB(A)
5.5
1 x SCROLL
1 x AXIAL
64
60
61
13
1 x SCROLL
1 x AXIAL
66
61
64
22
1 x SCROLL
1 x AXIAL
70
64
65
13 x 2
2 x SCROLL
2 x AXIAL
65
64
61
28 x 2
2 x SCROLL
2 x AXIAL
70
67
65
Dimensions
Width (unpacked)
Depth (unpacked)
Height (unpacked)
Weight (unpacked)
Width (export, packed)
Depth (export packed)
Height (export, packed)
Weight (export, packed)
mm
mm
mm
kg
mm
mm
mm
kg
1555
790
1080
247
1775
900
1250
268
1665
1060
1330
329
1845
1170
1500
346
1810
1190
1310
460
2020
1300
1480
571
2065
1190
1350
632
2265
1310
1520
747
2210
1650
1340
858
2470
1770
1505
1078
NOTES:
1) Weight and dimensions nett.
2) Allow 500mm clearance to service panels.
3) Minimum air temperature standard models (BH) 7°C.
4) Calorex reserve the right to change or modify models without prior notice.
5) Global warming potential (GWP) R134a 1300.
6) Performance data below 10°C is derated to account for defrost periods.
1 mm WG = 9.8 Pa
1 m hd = 1.4 psi
1 l/min = 0.22 gall/min