The parameter setting as shown on the following pages are programmed by
the supplier and should not need altering.
FAST PROGRAMMING OF SET POINT
Press the P key once then release it
“SP
” and set point value eg 26.0 will
be displayed alternately.
Press the up or down key to change the value of “SP”. Once the desired
value is displayed press P to memorise the value. The display will revert to
the present reading. If anything else shows on the display, leave it alone for
1 minute, until the display returns to normal.
Three options are available when accessing the instrument parameters.
1. STANDARD MODE PARAMETERS PROGRAMMING (ACCESSES ALL
PARAMETERS)
To prevent accidental changing of the thermostat, the parameters
are protected by the password -281
Press the P key and keep it pressed for about 5 seconds until display
shows r.P. Press P and the display shows “0”. Use the DOWN keys to set
the password -281. If you pass -281 then use the UP key to get back.
Once the correct password is entered press the P button again and the
display will show the first parameter “S.LS”.
Using the UP and DOWN keys, the desired parameter can be selected and
pressing the P key, the display will alternately show the parameter code
and its setting that can be changed with the UP and DOWN keys.
Once the desired value has been set, press the key P again: the new value
will be memorised and the display will show only the code of the selected
parameter.
Pressing the UP and DOWN keys, it is possible to select another
parameter and change it as described.
To exit the programming mode, do not press any key for about 30 seconds,
or keep the U key pressed for 2 sec. until it exits the programming mode.
2. TIMING PARAMETERS PROGRAMMING
These parameters are protected by the
password -181
this is accessed by
using the up and down keys the same way as described above, having
reached the request password point.
3. RESET TO ORIGINAL SETTINGS
The parameters can be reset to their original settings by entering the
password -481
which is reached in the same way as described above,
having reached the request password point. Once the password is confirmed
with the P key the display shows “---” for 2 seconds. The parameters are now
reset.
MANUAL DEFROST IS THIS TRUE FOR Y MACHINES?
It is possible to start or stop the heat pump defrosting through the thermostat.
Hold the Up key for 5 seconds. Defrost starts (or stops if defrosting).