5. TIME DELAY MODE

This heater is equipped with an internal compressor time delay to allow the refrigerant to
settle during start-up or restart cycles. When the heater is started the fan will run but the
compressor will not start until the 3 to 5 minute delay has passed. The green heating light
will be on when the compressor is running.   In some cases (when the heater is new or
during cold weather), it may be necessary to allow the unit to go through the time delay
several times before the unit will start. The unit will delay for other reasons noted below:

TIME DELAYS:

30 second compressor delay when switching pool/spa modes.

3 to 5 minute compressor delay when T.C.O. enables in pool mode.

5 minute T.C.O. off delay when: switching from spa to pool mode, when temperature is

reached in pool mode, or if LF (low water flow) is displayed on LED.
If water pump loses prime there will be a 3-5 minute compressor delay.

6. NORMAL OPERATION INDICATORS

When the fan and compressor are running, the unit will discharge cool air from the top.  The
heater will produce condensation while running and is considered normal. It will produce more
condensation the more humid the ambient air is.  The condensation will exit the heater through
the bottom drain ports.

7. POOL/SPA COVER USE

You can substantially reduce the heat loss and electrical consumption by utilizing a pool cover
or pool blanket.  You can get higher water temperatures in less operational time using a cover.  If
you keep the pool or spa covered whenever you are not swimming you can typically reduce
heat loss by as much as 80% and reduce heating costs as much as 50%.  Using a cover during the
initial heat up period will greatly reduce the operational time needed.

8. SPA HEATING

When heating a spa it is advisable to not run the air blower or air inlet venturis during the initial
heat up time.  Air blowers and venturis inject air into the water to create the spa therapy action.
During colder weather the air blower or inlet venturis will inject cold air into the spa thus increas-
ing heat demand.  Leaving these items off until the spa reaches the set temperature will reduce
the heat up time.  A cover is highly suggested for spa heating.

9. DEFROST CONTROL IN COLD WEATHER

DF

 

This readout indicates that the internal defrost safety control has disabled the heater.

During cold weather where the air temperature drops below approximately 45 to 50
degrees (depending on humidity), the low refrigerant pressure switch (or defrost con-
trol) is designed to disable the compressor only. Once the unit is in defrost mode the
compressor will shut off for 1 hour while the fan continues to help deice and warm the
air coil.  After 1 hour the unit will attempt to restart.  If the air temperature has increased
to the operational range the compressor will continue to run, otherwise the compressor
will return to the defrost mode for another 1 hour delay cycle.

You my experience some frost or icing on the outer air coil in cold weather tempera-
tures and is considered normal.  If the air coil ices up, shut the heater off, allow it to
defrost and wait for warmer weather to restart the heater.  If you live in an area where
the weather is expected to drop below 45˚F to 50˚F for an extended period you should
disable the heater during those times.

Page 7

Summary of Contents for Aquatherm DIGITAL LOGIC AT1000

Page 1: ...nge without notice NATIONAL POOL SPA INSTITUTE SWIMMING POOL SPA HEAT PUMPS NOTE Installers should see separate installation manual Model AT1000 AT800 AT600 AT400 BLACK CABINET with DIGITAL CONTROLS O...

Page 2: ...lations on the purchase of your new swimming pool spa heat pump Utilizing heat pump technology is the most efficent method of heating a swimming pool Please take a few minutes to read this owner s man...

Page 3: ...The liquid refrigerant in the air coil absorbs the available heat in the ambient air transforming it into a gas The refrigerant gas is then pumped into the compressor When this warmed gas is com pres...

Page 4: ...the water pump whenever the pool requires heat Once the pool is up to the set tempera ture the heater will stop and then 5 minutes later the water pump will stop When this button is set to the OFF mo...

Page 5: ...e water pump is off DF DEFROST MODE This readout indicates that the internal defrost safety control has disabled the heater During cold weather where the air temperature drops below approximately 45 t...

Page 6: ...D display will show a constant readout of the actual cur rent water temperature To set the desired water temperature press either the or thermostat buttons While adjusting the set temperature the LED...

Page 7: ...educe heat loss by as much as 80 and reduce heating costs as much as 50 Using a cover during the initial heat up period will greatly reduce the operational time needed 8 SPA HEATING When heating a spa...

Page 8: ...er is not restricted Make sure the unit can breathe well The cooler discharge air from the top should not accumulate and be drawn into the side air intake coils Keep all plants and shrubs trimmed away...

Page 9: ...IN THE POOL or SPA SKIMMER Chemicals placed in the skimmer will feed concentrated chemicals or chlorine into the heat exchanger before it is diluted with the rest of the pool water Chemicals or chlo r...

Page 10: ...p A minimal air coil cleaning should be done as needed and at least two times per year If the heater is installed in a sandy or salty condition the air coil should be cleaned more frequently 3 To clea...

Page 11: ...ns T Stat Relay Does Not Close Heater Does Not Activate After Delay Period Try Again or Possible Bad Time Delay Possible Bad T Stat Board Pot or Sensor 1 Hour Time Delay Activates Water Temperature is...

Page 12: ...or improper water balance Sprinkler damage Roof run off damage Freeze damage or operation damage during freezing conditions Salt and or sand debris damage Lack of maintenance and or cleaning Unauthor...

Reviews: