Water Pump
Starts Flowing
Water Pressure
SW Closes
Thermostat
Sensor
Heater
Stays Off
Low Pressure
Switch
Low Pressure
Switch Opens
LF displayed on LED
Low Pressure
SW Closed
All OK
LF Readout
Displayed on LED
T-Stat Relay
Closes
High Pressure
Switch
High Pressure
SW Closed
All OK
High Pressure
Switch Open
Heater Shuts Off
HP Displayed
Too Much Refrig.
or Low Water Flow
or Bad Hi Switch
Fan Starts
To Run, Green
Heating Light On
220V Power
To Heater
Green Power Light
On
Water Rises To
Set Temp.
Water Press. SW
Stays Open
No Water Flow
To Heater or
Bad Water SW
Compressor Runs
or 3 to 5 Min.
Delay Activates
Heater & Green
Heating
Light Go Off
Water Pump
Timer Activates
Compressor Stops
Fan Runs
T-Stat Relay
Does Not Close
Heater Does
Not Activate
After Delay Period
Try Again or
Possible Bad
Time Delay
Possible Bad
T-Stat Board, Pot
or Sensor
1 Hour Time Delay
Activates
Water Temperature
is Below Setting
Water Temperature
is Above Setting
Compressor Starts
Green Heating
Light ON
Time Delay Passes or
Air Temp. Increases
Safety Control Resets
Compressor
Restarts
or Below 45 to 50˚F
Air Temp or
Bad Low Press. Sw.
or Below 45 to 50
Deg. Air Temp
Operational Sequence & Troubleshooting Flow Chart
for “Digital Logic” Digital Control Models
TIME DELAYS
30 second compressor delay when switching pool/spa modes.
5 minute compressor delay when T.C.O. enables in pool mode.
5 minute T.C.O. off delay when: switching from spa to pool mode, when temperature is
reached in pool mode, or if LF (low water flow) is displayed on LED.
If water pump loses prime there will be a 3 minute compressor delay.
Page 11