background image

 

Summary of Contents for 500 Series

Page 1: ...Calix ONT Grounding Implementation January 2007 220 00178 Rev 10...

Page 2: ......

Page 3: ...Not for use or disclosure except by written agreement with Calix 2001 2007 Calix All Rights Reserved Contents Introduction 5 Grounding Purpose 5 NEC and Grounding 6 Testing the Earth Electrode 7 Full...

Page 4: ...4 Proprietary Information Not for use or disclosure except by written agreement with Calix 2001 2007 Calix All Rights Reserved...

Page 5: ...case would cause the over current device to trip thereby removing the power to the device y The protection and survivability of the electronics equipment High voltage spikes that occur during electric...

Page 6: ...The earth electrode can be a metallic cold water pipe or a copper clad steel rod that has been driven into the ground to a depth of at least 8 feet Metallic cold water pipes that run under ground for...

Page 7: ...depends on the chemical makeup and ambient moisture content of the soil The testing of an electrode measures the effectiveness of the earth electrode to provide electrical contact with the earth The...

Page 8: ...re measurements are taken beyond this point the amount of resistance to earth will start to increase again The test setup as illustrated below uses an Earth Resistance Megger to determine the resistan...

Page 9: ...ectrode being tested and the outer current electrode may be limited by the physical characteristic of the surrounding area or the length of the test conductor being used It is not uncommon for the out...

Page 10: ...should be kept for each ONT installation In some locations extremely high earth ground resistance is present In these locations chemicals that lower earth resistance can be added to the earth that sur...