background image

Exit Loops

Loop  wires  are  installed  1.5"  underground  by  cutting  the  concrete  with  a  circular  saw. 
The  typical  size  loop  is  8x4'.  Common  loop  wire

s  are  size 

16  or 

18  AWG

  stranded  copper 

XLPE (cross-linked polyethylene) 

electrical  wire

.  3  layers  of  turns  are  required  for  a  typical 

4x8' loop. 

For different size loops, use 4 turns for 10-20ft in perimeter, 3 turns for 20-32ft in 

perimeter, and 2 turns for 32-98ft in  perimeter. 

Place  a  plastic  foam

  or  backer  rods

  above 

the  loop  wire  turns  to  hold  it  in place.

 

Backer  rods  ensure  that  the  wires  are in place 

and do not vibrate. Any vibration of wire  movement  will  cause  a  false  detection. 

The 

wire 

ends  must  be  twisted  back  into  the  gate  operator  with  a  minimum  of  6  twists 
per  foot.  The  twisted  ends  must  be  placed  inside  a  PVC  conduit.  Use  sealant  to 
close  the  ground once finished.

Use a circular saw to create a saw cut on the ground.

Depth: 1.5"

Width: 0.2 - 0.3"

 

Make sure the 

edges are at a 45° 

angle

.

45°

Foam Backer Rods 1" spaced 1 feet apart on the top layer

Continuous (no splices)

 

loop 

w

ire 

with 3 turns

 placed directly on top 

of each other

PVC Conduit

Twisted 

Lead-

in 

Wires

 

leading into 

gate operator 

loop detector

4"

8"

Summary of Contents for CM9-603

Page 1: ... a reverse loop phantom loop and exit loop You will need a separate loop detector for each loop Loop wires go into the left side of the block terminal The terminal accepts loop wires for Exit Loops Phantom Loops and Reverse Loops Loop Wire PHANTOM SAFETY EXIT LOOP 24V COM 24 VDC Gate Operator Circuit Board Wiring ...

Page 2: ...erneath the gate operator chassis on the back of the power compartment You will see 4 transparent holes that you can use to drill in 4 screws not included Mount Loop Detector Harness Here Move the cable from the loop detector harness up into the circuit board compartment there will be a small circular hole large enough for the cable to go through Connect the wires based on the wiring diagram in th...

Page 3: ...ens the gate automatically when a car approaches the gate A reverse loop is a loop that reverses the direction of a closing gate if a car drives over it It will also hold a gate open if a vehicle stops over the loop If the gate is fully closed and a vehicle drives over it the gate will not open A phantom loop is a reverse loop located inside the property 8 FT 8 FT Exit Loops ...

Page 4: ...s to hold it in place Backer rods ensure that the wires are in place and do not vibrate Any vibration of wire movement will cause a false detection The wire ends must be twisted back into the gate operator with a minimum of 6 twists per foot The twisted ends must be placed inside a PVC conduit Use sealant to close the ground once finished Use a circular saw to create a saw cut on the ground Depth ...

Page 5: ...Exit Loops Loop wire 3 Turns Sealant Above Ground Backer Rod Loop Size Sq ft Number of Turns 6 to 12 6 61 to 240 3 2 5 21 to 60 4 0 2 241 1 5 13 to 20 ...

Reviews: