Page 19
5.2. Installing the Solida pellet stove
The following specifications regarding floor protection, distances from flammable
materials and the flue pipe connection may differ from regional and official regula-
tions. Please contact your Calimax sales partner or appropriate local authority if
there are any questions.
5.2.1. Floor protection
For practical cleaning aspects, it is recommended that the pellet stove is set up on a
fireproof base plate that is at least 5 cm wider than the back and sides of the stove
and extends at least 15 cm at the front.
It is not absolutely essential to have a fireproof base under the stove as excessive
temperatures are not produced in the lower section of the stove during operation.
The combustion chamber door is for cleaning purposes only and is not an ignition
door. It must not be opened during operation!
Please note the local regulations in all events, as they
may differ from the above specifications!
5.2.2. Distances from combustible materials
The following minimum distances from
combustible materials must be complied
with:
Back:
5 cm
Sides:
15 cm
Front:
80 cm
5.2.3. Flue connection
The flue must be connected to the chimney according to local regulations. Please
contact your Calimax sales partner or appropriate local authority if there are any
questions.
Do not lay any cables over the flue pipe!
The minimum draught requirement in the chimney must be greater than 0 Pa!