Troubleshooting
1.
Turn off power before beginning. Check for any twisting or damage to
the wire on the light string.
2.
Check for metal particles or other foreign objects causing the short.
4.
Ensure the lead wire is not too long and wound or coiled.
5.
Ensure copper wires are not touching each other or strain relief cable.
6.
Ensure there are no missing or broken bulbs from light string.
Broken bulb
Missing bulb
<1.5”
<1.5”
<1.5”
Knicks in
wire jacket
<1.5”
Coiled wire
Frayed end will cause a short
when wires or cables touch
<1.5”
Check end cap for any
metal particles before
committing to end of run
3.
Check if cut is not frayed, causing hot and neutral wires to touch.
<1.5”
Frayed end
TROUBLESHOOT
• Do not reset breaker multiple times.
• If the lighting is overloaded, the panel breaker will trip,
shutting off the lights.
• If the breaker reset button has been held down by hand or any type
of pressure (example: duct tape), or if the breaker has been reset
multiple times without trouble shooting, the lighting will:
- Burn the primary wires due to high amperage caused
by overload and/ or short circuit in line which will not allow the
panel breaker to reset
- Damage the lighting