5

Dimensions

B

B’

Code

A

B

B'*

C

D

Wt (lb/kg)

116

140A(C)

½" NPT F

4

"

7

/16

"

¾" 

3" 

1.7 / 0.75

116

141A(C)**

½" NPT F

4

"

7

/16

"

¾" 

3" 

1.7 / 0.75

116

150A(C)

¾" NPT F

4

"

5

/8

"

¾" 

3" 

1.5 / 0.70

116

151A(C)**

¾" NPT F

4

"

5

/8

"

¾" 

3" 

1.5 / 0.70

*Models with check valve tail-piece (C) end-to-end dimension is B'. 
**with integral outlet temperature gauge.

The ThermoSetter thermostatic balancing valve is designed to balance individual branches of 
domestic hot water recirculation systems, based on the temperature at the valve. It automatically 
modulates flow to maintain hot water availability to all fixtures in the branch circuit. The valve is at 
minimum flow (Cv = .35) when the incoming water temperature is equal to the set-point position 
of the adjustment dial. The valve opens as incoming water temperature drops. 
For pressure loss calculations 
in the recirculation system, 
follow traditional pipe sizing 
and head loss practices. 
For pressure loss calculations 
across the ThermoSetter 
valve, use the design curve 
shown in the graph below. 
This line represents a typical 
valve position under normal 
working conditions (∆T= 
10°F). Determine the pressure 
drop across the valve by 
selecting the branch design 
GPM on the graph X-axis, 
draw a vertical line up to 
the “design” curve, then go 
across to the Y-axis to find 
the design pressure drop. 
Include that pressure drop 
in your head loss calculations 
for the circuit.

Flow characteristics

2. 5

3

4.5

6 7 8.810 12

13.2

0.01

0.02

0.03

0.05

0.07

0.10

0.15

0.20

0.30

0.50

0.70

1.00

1.50

2.00

3.00

4

5

6

7.25

10

14.5

0.70

2.00

Flow rate

(/m)

 (gpm)

0.40

0.30 

0.12 

0.10 

0.08

 

1.40

1.80

0.90

0.60

0.30

1.20

0.16 

0.20 

0.50

0.60

0.90

1.00

1.80

0.36

0.48

2.40

3.00

3.60

4.20

4.80

5.40

6.00

7.80

p (psi)

∆p (kPa)

0.1

0.2

0.3

0.5

0.7

1.0

1.4

 2.0

3.5

7.0

11

13

20

10

˚

T

inlet to setpoint

Operation in 

by-pass mode

0.35 Cv

minimum

2.1 Cv

full open

0.69 Cv

 design

Summary of Contents for ThermoSetter 116140A

Page 1: ...ge w and w o check valve connections and NPT female www caleffi com The valve is ICC ES certified to NSF ANSI 61 180 F 82 C Commercial Hot and NSF ANSI 372 low lead laws It meets codes IPC IRC UPC and...

Page 2: ...ubricity so that care must be exercised not to over tighten joints Failure to follow these instructions could result in property damage and or personal injury WARNING System fluids are under pressure...

Page 3: ...la temp rature peuvent tre dangereux tre s r que la pression a t r duite z ro et la temp rature du syst me est inf rieure 100 F 38 C Le non respect de ces instructions peut entra ner des dommages mat...

Page 4: ...imum position Cvmax T F G gpm Cvmin 100 140 150 160 190 170 180 185 Tset 2 1 0 35 Cvdesign 0 69 1 2 3 1 2 3 1 2 3 Thermostatic control 1164xxA series Thermostatic control with check valve 11614xAC ser...

Page 5: ...lation system follow traditional pipe sizing and head loss practices For pressurelosscalculations across the ThermoSetter valve use the design curve shown in the graph below This line represents a typ...

Page 6: ...the top of the adjustment knob remove the knob and then put it back on so that the internal groove couples with the protrusion on the knob holder nut When this block is used the reference of the Main...

Page 7: ...7 Application diagram 135 F 135 F 135 F 140 F 120 F NOTE Do not set at temperatures 120 F if anti scald valves are not installed at the xtures Hot water recirculation with thermal balancing valves...